U01 Cool-down Start Time
(hh:mm)
Saturday > 6:00
Sunday
> 6:00
Duration > 60min
If Morning Cool-Down is enabled, the Morning Cool-Down
Start Time will appear under the Schedule sub-menu for
each Day of the Week There is also a Duration Time in
minutes that needs to be set The Cool-Down then starts at
the Cool-Down Start Time for that particular Day and be in
Morning Cool-Down Mode until either the Cool-Down Set
Point is achieved or until the Duration Time expires
Set-Back
Under the Set Back sub-menu, the following screens appear
to allow set up of the Set Back feature to allow each Mode
of Operation to work in the Set Back Mode
U01
Enable Set - Back
Control
Cooling >Yes
Heating >Yes
Dehumidify >Yes
Humidify >Yes
Enable each of the Modes of Operation that should operate
during the Set-Back Mode The enable points and set points
follow the same principle Cooling will automatically appear
Heating will only appear if heaters are enabled within the
Factory Menu. Dehumidification will appear when either
the Return Humidity or Space Humidity Sensor is enabled,
and Humidification will only appear when either the Return
Humidity or Space Humidity is enabled and a Humidifier is
installed
U01 Set-Back
Cooling
Setpoint > 76.0 °F
Prop Band > 02.0 °F
U01 Set-Back
Dehumidification
Setpoint > 55.0%
Prop Band> 05.0%
U01 Set-Back
Heating
Setpoint > 70.0 °F