Marvel Mini™ - Controllable System Component Information
With this new format, one of the key benefits of the Marvel Mini™ application software is set up universally so that any of the
following functions could literally be added to any of the corresponding channels This means for example, any of the listed
functions under Analog/Universal Inputs could be placed onto any of the Universal Channels U1 though U10 whereas in
the past and with most control vendors, a software modification would be required. In addition now all of the Analog Inputs,
Digital Inputs, Analog Outputs, and Digital Outputs are all selectable for any of their corresponding channels So for instance
the digital output for Compressor 1 could be configured on any of the Digital Outputs NO1 through NO18 (example of large
controller maximum number of Digital Outputs) These Universal Functions for each of the four I/O Groups are:
ANALOG/UNIVERSAL INPUTS
Return Temperature
Compressor 1 Liquid Temperature
Compressor Liquid Pressure
Space Temperature
Compressor 1 Suction Temperature
Space Humidity
Outdoor Air Temperature
Water Temperature
Outdoor Air Humidity
Supply Air Temperature 1
Return Humidity
ANALOG OUTPUTS
Modulating Hot Gas Bypass
Modulating Waterside Economizer
Discharge Pressure Valve 1
Airside Economizer
Modulating Reheat
Modulating Heater
Modulating Humidifier
DIGITAL INPUTS
Compressor 1 High Pressure
Remote ON/OFF
Heater High Limit
Compressor 1 Low Pressure
Dirty Filter
Water Flow
Loss of Airflow
Compressor Freeze Stat
Smoke Purge
Drain Pan Overflow
Fire/Smoke Alarm
Heat Pump Defrost Switch
DIGITAL OUTPUTS
Supply Blower
Heater
Global Alarm Output
Outdoor/Fresh Air Damper
Reversing Valve
Compressor
Reheat