Installation, Operation and Maintenance Manual
Marvel Mini
62
Subject to change without notice.
120.9-IM (1218)
3
If the units were ordered from the factory as a
networking system, the following procedure will have
already been completed and tested Each unit must be
shared with the Marvel Terminal/Wall Display In order
to do this, disconnect power to all but one unit Each
unit will be updated one at a time
4
Press the (up), (down) (enter) and buttons
simultaneously for 5 seconds until the following screen
appears
Display address
setting............ :32
I/O Board address: 01
5
Make sure the display address it set to a 32 On the
present unit being updated, the I/O Board address
should automatically appear If it does not appear, a
-- will appear Simply position the blinking cursor over
the -- by pressing the (enter) it is positioned at this
location Press the up or down button until the pLAN
address shown in Figure 20 appears at this location
Press the (enter) button until the next screen
appears and then once this screen appears, press the
(enter) button again till the Priv/Shared Screen as
shown appears
Terminal config
Press ENTER
To Continue
6
Trm1 must be a value of 32 to match the value
previously set If it is not a 32, use the (up) or
(down) buttons to change the value to a 32 then press
the (enter) button to save it into memory Next,
use the (up) or (down) buttons to change the
value under Priv to make sure that if Pr is displayed,
the value must be Sh for Shared and then press the
(enter) button to save it into memory Continue to
press the (enter) button until the blinking cursor is
positioned under the NO and use the (up) button
to change the value to Yes. Once this is finished, the
main status screen will reappear
P:01 Adr Priv/Shared
Trm1 32
Sh
Trm2 None --
Trm3 None -- ok?NO
7
At this point, power this unit down and repeat the
previous steps to share each unit with the Marvel
Terminal It is easiest to do one unit at a time making
sure that power is applied only to the unit being
updated Once all units have been updated, power can
be applied to all units