BATTERY CHARGER USER’S MANUAL PART- 2: THEORY OF OPERATION
MCEnPC23-REV.2.4
Page 75
xxviii.
Unbalanced Battery Alarm **
Unbalanced Battery alarm is activated if one or more battery cells are defective. VCell is the voltage unbalancing
(Error) allowed for one cell/ block before this alarm will be active. If the maximum allowable voltage exceeds the
preset value for VCell, during a preset time, than this alarm will be activated. We can enable or disable and adjust
this alarm as shown on the procedure below:
Alarms?
Ok
Next
Pr
Exit
Adjust?
Level1
Ok
Next
Pr
Exit
ON
V
0.7
VCell
Set
Exit
Next
Pr
ON
OFF
Next
Exit
:
get
you
Next till
Press
Next
Exit
-
ON
VCell
Cell
Defective
10.0A
136.2V
:
get
you
Next till
Press
ON
V
0.7
VCell
Figure 77 : Unbalanced Battery Alarm adjustments procedure.
* : Included, enabled upon customer request only. Can also be field activated
** : Optional