BATTERY CHARGER USER’S MANUAL PART- 2: THEORY OF OPERATION
MCEnPC23-REV.2.4
Page 32
vi.
AC Fail Equalize (optional)
If enabled, then the charger will go into “Equalize” mode after an AC mains failure. Equalize cycle will be during a
period of time between 1 and 8191 hours. We can enable or disable and adjust AC fail Equalize as follows:
Control?
Ok
Next
Pr
Exit
Adjust?
Level1
Ok
Next
Pr
Exit
Eq
Start
Set
Exit
Next
Pr
ON
ACEq
Set
Exit
Next
Pr
ON
OFF
Out
Time
Next
Exit
08H
:
get
you
Next till
Press
:
get
you
Next till
Press
Next
Exit
-
ON
ACEq
Delay
S
10
Next
Exit
-
Figure 35 : Procedure to enable or disable and adjust AC Fail Equalize.
Delay =10 seconds: in this example, this delay represent the AC failure duration. If the failure persists more than 10
seconds, the battery charger will switch automatically to Equalize mode for 8 hours (Time Out) when AC input will
be re-established.