Page 31 of 39
Rev. 13
3.5 CHARGER COMMON PARAMETERS SET UP
3.5.1 GENERAL
Select (function 3), Operate (function 4), Direct operation (function 5), Direct operation no acknowledge, with Object 41
variation 01 or 02, allows to modify the charger operating parameters.
In this paragraph, we present the most common charger settings. For more information, please contact the factory.
All points are coded in 16 bits.
Only qualified and trained personnel can access this mapping.
Parameters modification with wrong information may lead to major defects and failures if wrong data is used.
3.5.2 VOLTAGE OR CURRENT SETTINGS
In order to modify the float voltage, write the required value in point 1 (Refer to
Note1
, for the byte format to send).
For equalize voltage, the point 2 is to be used.
In order to modify the float current limit, write the required value in point 3 (Refer to
Note1
, for the byte format to send).
For equalize current limit, the point 4 is to be used.
3.5.3 CHARGER CONFIGURATION
Please do not modify this register without consulting the factory. To modify the charger configuration, write the required
value in point 5, the byte format to send is the following:
MSB LSB
15 14 13 12 11 10
9
8
7
6
5
4
3 2 1
0
0: ON/OFF display
1: Load sharing
2: Temperature compensation
3: AC current display
4: AC voltage display
5: LCD sleep mode
6: Language
7: Battery current display
8 Formation
9: Battery test
10: x
11: x
12: x
13: x
14: x
15: x
3.5.4 ALARM RESET
To reset all alarms, send (01 in binary) into the point 90L.
Содержание ARR-M Series
Страница 2: ... i BATTERY CHARGER USER S MANUAL ...
Страница 5: ... iv FIGURE LIST 86 ACRONYM LIST 88 LCD MESSAGES LIST 90 APPENDIXES 92 ...
Страница 6: ...MCEnPC23 REV 2 4 Page 1 PART 1 INSTALLATION INSTALLATION ...
Страница 10: ...MCEnPC23 REV 2 4 Page 5 PART 2 THEORY OF OPERATION THEORYOFOPERATION ...
Страница 98: ...Page 1 of 39 Rev 13 Communication User Manual Appendix 3 27 01 2015 ...