14: AC low volt
15: x
This register is used to configure the alarm relay in fail-safe (de-energized when alarm occurs) or non fail-safe
(energized when alarm occurs)
Note 20
Fail-safe or non-fail safe alarm relays operation address: (31 hex)
15 14 13 12 11 10
9
8
7
6
5
4
3 2 1
0
0: Battery cell failure
1: AC fail
2: High ripple
3: High DC current
4: Low DC current
5: Equalize alarm
6: Mains frequency failure
7: Battery cell failure
8: High current battery
9: Low current battery
10: High capacity
11: Low capacity
12: x
13: x
14: Common alarm
15: x
This register is used to configure the alarm relay in fail-safe (de-energized when alarm occurs) or non fail-safe
(energized when alarm occurs)
Note 21
Charger mode enabling- address: (26 hex)
15 14 13 12 11 10
9
8
7
6
5
4
3 2 1
0
0: Remote equalize
1: Remote float
2: Formation
3: Battery test
4: x
5: x
6: x
7: x
8: x
9: x
10: x
11: x
12: x
13: x
14: x
15: x
This register is used to force the charger in one of the above operation modes.
Note 22
Variables are coded in 2 bytes.