UniPOS
Wireless Fire Alarm Control Panel VIT 01
Instruction manual
Page 31
Revision 10/02.17
Pages 51
Press buttons
and
to make a selection from the submenu, button
returns the
display in menu
„Zones”.
12.4.2.2.1. Parameter
„Zone name”
Enter the name character by character.
The following buttons are used:
buttons
and
to select the
specific character from the set of
characters;
button
- to move to entering the
next character of the name;
button
- to exit in menu
„Zones”.
The maximum number of characters is 8. After inserting the last character, press button
, to
save tha name and proceed to the next parameter.
Holding down button
also saves the introduced name, without the need of entering a maximum
number of characters.
Depending on the selected language, the possible sets of characters are different:
for Bulgarian
: _АБВГДЕЖЗИЙКЛМНОПРСТУФХЦЧШЩЪЬЮЯ-9876543210;
for English and Italian: _ABCDEFGHIJKLMNOPQRSTUVWXYZ-9876543210;
.
12.4.2.2.2. Parameter
„Inspection time”
The inspection time is additionally added
time (in seconds), that the user could activate in
order to make a physical check upon released
signal for fire condition. Inspection time shall be
added to the time period between phases
„Fire
1” and „Fire 2”.
Active buttons are:
buttons
and
- for
changing the parameter value;
button
- for saving and moving
to the next parameter;
button
- to exit menu in
„Zones”.
The parameter accepts values from 0 to 240. Default value is 0 seconds.
12.4.2.2.3. Parameter
„ Time period P1-P2”
The parameter sets the time (in seconds)
between phases
„Fire 1” and „Fire 2”.
Active buttons are:
buttons
and
- for
changing the parameter value;
button
- for saving and moving
to the next parameter;
button
- to exit menu in
„Zones”.
The parameter accepts values from 0 to 240.
Default value - 60 seconds.