Upon registering of fault condition, relay
„REL
Fault” is activated.
Entering Fire condition of Control Panel
suppresses the messages of fault condition.
The display shows information about the type of
the fault and the total number of faults.
(
Example: Fault in the Back up batteries supply.
Total number of faults
– 2. The common indicator
for fault condition is illuminated
, the
specialized indicator
and the local indicator
for fault conditionin zone 7.The second fault can
be reviewed by using buttons “Up” and “Down”
).
8.3. Using the keypad
There are no active buttons in fatal fault condition.
For the other fault conditions are used 4 active buttons. When the Fire Control Panel is in a
combination with other conditions are active their corresponding buttons.
Button
Access
Level
Action
Additional information
Button
(“Alarm”)
All
Pressing the button:
-
switches
off
the
local
sounder;
-
activates the local sounder,
if the Control Panel has
entered Fire or Fault
condition, and the local
sounder was switched off by
previous pressing of this
button.
The action of the button is
reversible i.e by single pressing
changes the current condition
respectively
– switched off or
switched on sounder.
The
LED
indicator
is
illuminated
if
the
condition
switched off sounder is active.
The
local
sounder
is
activated again:
-
upon
entering
Fire
condition of the Control
Panel;
-
in occurance of a new
fault or fire.
Buttons
(„Up”
and
„Down”)
и
All
Display information about fault
conditions, if more than one fault is
registered.
Button
(“Menu”)
All
Pressing
the
button
enters
Information and control.
Check the condition of the
fire detectors and the current fault
conditions.
9. Disabled component condition
9.1. Description
The Fire Control Panel enters Disabled component condition after manual operation of disabling
an element of the Fire alarm system
– a fire detector or a routers (controller).
Operations for disabling shall be performed in Set Up mode at access level 2 or higher.
Upon disabling an output, it can not be activated in any circumstances and it is not monitored for
fault condition.
Operations on disabling elements are described in “Set Up” condition.