UniPOS
Wireless Fire Alarm Control Panel VIT 01
Instruction manual
Page 16
Revision 10/02.17
Pages 51
- Number and user description name of the zone (Example:
01 Floor1
) to which
detector belongs;
- At phase 1
– the time in seconds, remaining to entering phase 2 (
Example:
33
).
On the 3
rd
and 4
th
line
– corresponding information about the last activated fire (if they are more
than one) or duplicated information from the two lines above (if the activated fire detector is only
one).
The Control Panel enters
„Fire condition 2” after the set time between phase 1 and phase 2
expires. Default time between phase 1 and phase 2 is 60 seconds and can be change from
parameters of the zone.
Proceeding to
„Fire condition 2” is performed immediately in the following cases:
the set time Phase1-Phase2 and the inspection time are 0.
the fire condition signal comes from FD type VIT50 and parameter
„Manual Call point priority”
of the zone is set to
„Yes”.
button
is held down more than 5 seconds.
7.3. Using the keypad
Actions on using with buttons apply to all the areas, where the fire condition occurs.
Button
Access
Level
Action
Additional information
Button
(“Alarm”)
All
Pressing the button :
-
switched
off
the
local
sounder ;
-
activates the local sounder,
if the Control Panel has
entered Fire condition or
Fault condition, and the local
sounder was muted by
previous pressing of the
same button.
The action of the button is
reversible i.e by single pressing
changes the current condition
respectively
– switched off or
switched on sounder.
LED indicator is illuminated if
the
condition
switched
off
sounder is active.
The
local
sounder
is
activated again:
-
upon
entering
Fire
condition of the Control
Panel from a new zone;
-
in occurance of a new
fault or fire.
Button
(“Outputs”)
2
nd
or
higher
Pressing the button:
suppresses
the
outputs,
switched off , in case of Fire
condition;
activates
the
suppressed
outputs if there are any;
in case the Control Panel is
in Fire 1, it goes to to Fire 2
if the button was held down
for more than 5 seconds.
Operating with the button
requires access level 2 or higher.
The action of the button is
reversible i.e by single pressing
changes the current condition
respectively
– suppressed or
activated outputs.
LED indicator is illuminated if
the condition suppressed outputs
is active.