7: Options
7-2
UPS338-01-00 PowerWAVE 8000-RI DPA User Manual Dated 5 April 2013
7.3
Generator ON facilities
The generator ON facility must use a normally-open contact which closes to indicate that a generator is
running and supplying the UPS input power.
When used, this facility enables the option to inhibit the operation of the battery charger and/or static bypass.
See “Set-up User menu screen” in section 4.3.8.
1. Use a screened cable with 1 pair (section of wires 0.6 mm2) and maximum length of 100 m.
2. Connect the cable as shown in Figure 7.2.
Figure 7.2 Generator ON Connection
7.4
WAVEMON Shutdown and Management Software
7.4.1 Why is UPS Management important?
By combining a UPS with a variety of network management products, such as orderly shutdown software and
SNMP adaptors, system-administrators can be assured that their electricity supplies are monitored for power
disruptions and depleted battery conditions. Such conditions pose the greatest threat through power
disturbance to valuable computer data by causing possible corruption or loss. By installing UPS/Mains
monitoring software, administrators are able to monitor the utility power from a central location, allowing early
warning of problems even across more complex systems like Wide Area Networks (WAN) and Enterprise
Wide Networks of multinational companies.
A prolonged mains failure may outlast the battery autonomy of the UPS system. If this situation occurs the
UPS management software will initiate an automatic, ‘controlled’ shutdown of the operating system, and so
protect valuable data.
Uninterruptible Power Supplies Ltd offer a wide range of local and remote monitoring and control systems,
affording maximum protection for computer systems.
7.4.2 WAVEMON Shutdown and Monitoring Software
WAVEMON is an external monitoring and shutdown software which is designed to operate with many of
Uninterruptible Power Supplies Ltd UPS products, both with the dry port (Relays) on terminal block X2 and
RS232 port JD1 on the communications card.
The software package consists of a CD ROM for most commonly used operating systems, a standard cable
set and a user manual.
X1
X1/1
X1/2
ON Generator
Terminal block
UPS ‘Generator On’
Port
X1
Содержание PowerWAVE 8000DPA RI
Страница 1: ...User Manual PowerWAVE 8000DPA RI Pioneering solutions for total power protection ...
Страница 2: ...UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 ...
Страница 4: ...UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 ...
Страница 8: ... iv UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 ...
Страница 10: ...1 Safety 1 2 UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 ...
Страница 16: ...2 General Description 2 6 UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 ...
Страница 21: ...UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 3 5 3 Installation RI 10 TYPE x1 Figure 3 2 ...
Страница 22: ...3 Installation 3 6 UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 RI 11 TYPE1 Figure 3 3 ...
Страница 23: ...UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 3 7 3 Installation RI 12 TYPE 2 Figure 3 4 ...
Страница 24: ...3 Installation 3 8 UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 RI 20 TYPE x2 Figure 3 5 ...
Страница 25: ...UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 3 9 3 Installation RI 22 TYPE3 Figure 3 6 ...
Страница 26: ...3 Installation 3 10 UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 RI 24 TYPE 4 Figure 3 7 ...
Страница 27: ...UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 3 11 3 Installation Figure 3 8 RI 40 Type X4 ...
Страница 28: ...3 Installation 3 12 UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 Figure 3 9 RI 40 Type X4 ...
Страница 42: ...3 Installation 3 26 UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 ...