UPS338-01-00 PowerWAVE 8000-RI DPA User Manual Dated 5 April 2013
3-3
3: Installation
3.5.2 Battery
The UPS utilizes sealed, maintenance-free batteries, whose storage capability depends on ambient
temperature. It is therefore important not to store the UPS for longer than 6 months at 20°C, 3 months at
30°C and 2 months at 35°C storage temperature without a battery recharge. For longer term storage make
sure that the battery is fully recharged every 6 months @20°C.
3.6
Positioning
3.6.1 Planning the installation
A certain amount of pre-planning will help ensure smooth, trouble-free equipment installation. The following
guidelines should be taken into account when planning a suitable UPS location and environment.
1. The equipment must be installed and transported in a upright position.
2. The floor at the installed location and en-route from the off-loading point must be able to safely take the
weight of the UPS and battery equipment plus fork lift during transit.
3. The UPS requires space at the bottom (front and back) to enable cooling airflow. Suitable ventilation
airflow must be provided
(See Figure 3.1)
.
4. All parts of the UPS required for maintenance, service and user operation are accessible from the front
and rear, making it a service-friendly and maintenance-friendly. Reserve a minimum of 900mm space at
the rear and 1000mm at the front of the UPS cabinet.
5. An ambient temperature of 20°C is recommended to achieve a long battery life. The cooling air entering
the UPS must not 40°C.
6. Avoid high ambient temperature, moisture and humidity. The floor material should be non-flammable and
strong enough to support the heavy load.
7. In summary, the UPS should be located where:
a) Humidity (< 90% non-condensing) and temperature (+15°C to +25°C) are within prescribed limits.
b) Fire protection standards are respected.
c) Cabling can be performed easily.
d) Minimum 1000mm front accessibility is available for service or periodic maintenance. There should
also be a minimum 900mm clearance at the rear to enable access to the power connections.
e) The air conditioning system has a sufficient amount of air cooling to keep the maximum room
temperature rise at a desired level and the required air cooling flow is available.
f)
No dust or corrosive/explosive gases are present.
g) The location is vibration free.
h) If the UPS will be installed in bayed enclosures, partition walls have to be installed.
CAUTION: Sealed batteries must never be stored in a discharged or partially discharged state.
Extreme temperature, under-charge and overcharge and over-discharge will destroy batteries!
Key Point:
Note the following:
•
Charge the battery both before and after storing.
•
Always store the batteries in a dry, clean, cool environment in their original packaging.
•
If the packaging is removed protect the batteries from dust and humidity.
Содержание PowerWAVE 8000DPA RI
Страница 1: ...User Manual PowerWAVE 8000DPA RI Pioneering solutions for total power protection ...
Страница 2: ...UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 ...
Страница 4: ...UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 ...
Страница 8: ... iv UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 ...
Страница 10: ...1 Safety 1 2 UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 ...
Страница 16: ...2 General Description 2 6 UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 ...
Страница 21: ...UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 3 5 3 Installation RI 10 TYPE x1 Figure 3 2 ...
Страница 22: ...3 Installation 3 6 UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 RI 11 TYPE1 Figure 3 3 ...
Страница 23: ...UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 3 7 3 Installation RI 12 TYPE 2 Figure 3 4 ...
Страница 24: ...3 Installation 3 8 UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 RI 20 TYPE x2 Figure 3 5 ...
Страница 25: ...UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 3 9 3 Installation RI 22 TYPE3 Figure 3 6 ...
Страница 26: ...3 Installation 3 10 UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 RI 24 TYPE 4 Figure 3 7 ...
Страница 27: ...UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 3 11 3 Installation Figure 3 8 RI 40 Type X4 ...
Страница 28: ...3 Installation 3 12 UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 Figure 3 9 RI 40 Type X4 ...
Страница 42: ...3 Installation 3 26 UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 ...