36
In the example the Gmod gas train has been set (Configuration “1”).
Choose the fuel train by pressing ENTER, then press “
+
” / “
-
”. Press ENTER to confirm: number “1” will appear on the right side of the
display.
Then press ESC
to quit. The following display is:
Press “
+
” to show the first point to be set P0.
Press
F
and
“+”
to increase the opening angle of the fuel actuator “
0F”
until the requested value is reached (for example
12
°
÷15°
, see
below) for the ignition point; or press
F
and
“-”
to decrease the angle:
To set the air damper opening angle “0A” in the ignition point (
1
0
° for example - see below), press “A” and “+” “A” and “-” at the
same
time:
LMV37:
Now the air and fuel quantities are set at the ignition point P0:
By pressing “+”, point P9 can be programmed to set the air and fuel values at the maximum output
go on as described above to the the opening angles of the air actuator (A) and fuel actuator (F):
Lo 3-stage
Содержание LX60
Страница 35: ...PART IV MAINTENANCE 35 Fig 28 Fig 29 Fig 30 B A C D E...
Страница 41: ......
Страница 42: ......
Страница 43: ......
Страница 45: ...Service manual AZL2x LMV2x 3x Burner Management System M12916CD Rev 3 4 03 2023...
Страница 52: ...8 Parameters level heating engineer...
Страница 94: ...50 ERROR CODE TABLE...
Страница 95: ...51...
Страница 96: ...52...
Страница 97: ...53...
Страница 98: ...54...
Страница 99: ...55...
Страница 100: ...56...
Страница 101: ...57...
Страница 102: ...58...
Страница 103: ...59...
Страница 104: ...60...
Страница 105: ...61...
Страница 106: ...62...
Страница 107: ...63...
Страница 108: ...64...
Страница 110: ...66 Wiring variants for LMV27 2 Fuel meter input 1 Supply fuel meter ConnectorX75 ConnectorX5 02 ConnectionsPmax...
Страница 113: ......
Страница 114: ......
Страница 115: ......