PART II: INSTALLATION
19
Pressure adjusting range
The pressure adjusting range, downstream the gas valves group, changes according to the spring provided with the valve group.
Keys
1 spring
2 cap
Siemens VGD valves with SKP actuator:
Once the gas train in installed, execute the electrical connections for all its items (gas valves group, gas proving system, pressure
switches).
Gas Filter (if provided)
The gas filters remove the dust particles that are present in the gas, and prevent the elements at risk (e.g.: burner valves, counters and
regulators) from becoming rapidly blocked. The filter is normally installed upstream from all the control and on-off devices.
Siemens SKP actuator
Performance range (mbar)
0 - 22
15 - 120
100 - 250
Spring colour
neutral
yellow
red
ATTENTION: it is reccomended to install the filter with gas flow parallel to the floor in order to prevent dust fall
on the safety valve during maintenance operation.
2
1
Содержание LX60
Страница 35: ...PART IV MAINTENANCE 35 Fig 28 Fig 29 Fig 30 B A C D E...
Страница 41: ......
Страница 42: ......
Страница 43: ......
Страница 45: ...Service manual AZL2x LMV2x 3x Burner Management System M12916CD Rev 3 4 03 2023...
Страница 52: ...8 Parameters level heating engineer...
Страница 94: ...50 ERROR CODE TABLE...
Страница 95: ...51...
Страница 96: ...52...
Страница 97: ...53...
Страница 98: ...54...
Страница 99: ...55...
Страница 100: ...56...
Страница 101: ...57...
Страница 102: ...58...
Страница 103: ...59...
Страница 104: ...60...
Страница 105: ...61...
Страница 106: ...62...
Страница 107: ...63...
Страница 108: ...64...
Страница 110: ...66 Wiring variants for LMV27 2 Fuel meter input 1 Supply fuel meter ConnectorX75 ConnectorX5 02 ConnectionsPmax...
Страница 113: ......
Страница 114: ......
Страница 115: ......