PART I: SPECIFICATIONS
6
Technical Specifications
(*) NOTE ON THE BURNER WORKING SERVICE:
LMV2x automatically stops after 24h of continuous working. The device immedia-
telystarts up, automatically. LMV3x performs countinuous operation.
BURNERS
LX60 M-...0.40
LX60 M-...0.50
LX60 M-...0.65
Output
min. - max kW
165 - 720
Fuel
Natural gas
Category
(see next paragraph)
Gas rate
min.- max Stm
3
/h
17.5 - 76
Gas pressure
min. - max. mbar
(see Note 2)
Power supply
400V 3N ~ 50Hz
Total power consumption
kW
1.6
Electric motor)
kW
1.1
Protection
IP40
Approx. weight
kg
58
58
65
Operation
Progressive - Fully modulating
Valves size / Gas connection
1"
1/2
/ Rp1
1/2
2" / Rp2
2"
1/2
/ DN65
Operating temperature
°C
-10 ÷ +50
Storage Temperature
°C
-20 ÷ +60
Working service *
Intermittent
BURNERS
LX65 M-...0.50
LX65 M-...0.65
Output
min. - max kW
245 - 760
Fuel
Natural gas
Category
(see next paragraph)
Gas rate
min.- max Stm
3
/h
26 - 80
Gas pressure
min. - max. mbar
(see Note 2)
Power supply
400V 3N ~ 50Hz
Total power consumption
kW
2
Electric motor)
kW
1.5
Protection
IP40
Approx. weight
kg
80
95
Operation
Progressive - Fully modulating
Valves size / Gas connection
2" / Rp2
2"
1/2
/ DN65
Operating temperature
°C
-10 ÷ +50
Storage Temperature
°C
-20 ÷ +60
Working service *
Intermittent
Note1:
All gas flow rates are referred to Stm
3
/h (1013 mbar absolute pressure, 15 °C temperature) and are valid for G20 gas
(net calorific value H
i
= 34.02 MJ/Stm
3
);
Note2:
Maximum gas pressure = 360mbar (with
Dungs MBDLE)
Maximum gas pressure = 500mbar (with
Siemens VGD)
Minimum gas pressure = see gas curves.
Содержание LX60
Страница 35: ...PART IV MAINTENANCE 35 Fig 28 Fig 29 Fig 30 B A C D E...
Страница 41: ......
Страница 42: ......
Страница 43: ......
Страница 45: ...Service manual AZL2x LMV2x 3x Burner Management System M12916CD Rev 3 4 03 2023...
Страница 52: ...8 Parameters level heating engineer...
Страница 94: ...50 ERROR CODE TABLE...
Страница 95: ...51...
Страница 96: ...52...
Страница 97: ...53...
Страница 98: ...54...
Страница 99: ...55...
Страница 100: ...56...
Страница 101: ...57...
Страница 102: ...58...
Страница 103: ...59...
Страница 104: ...60...
Страница 105: ...61...
Страница 106: ...62...
Страница 107: ...63...
Страница 108: ...64...
Страница 110: ...66 Wiring variants for LMV27 2 Fuel meter input 1 Supply fuel meter ConnectorX75 ConnectorX5 02 ConnectionsPmax...
Страница 113: ......
Страница 114: ......
Страница 115: ......