Uni-P H20 200C DEHUMIDIFIER
Installation, Operation & Service Instructions
Uni-P H20 200C DEHUMIDIFIER
Installation, Operation & Service Instructions
Supply
Duct
Kit
(
P
/
N
4028607
)
A factory designed supply kit can be bought to match the 10” ducting to both inlet and outlet
of the Uni-P H2O 200CC.
You can contact the manufacturer or may find it at your local dealer’s store.
The P/N 4028610 Return Duct Kit
A factory designed return kit can be bought to match the 12” ducting of the device.
You can call the manufacturer or may find it at your local dealer’s store.
The condensing unit demands that a dedicated 20 Amp 120VAC circuit capacity. Makes sure
you install a well-sized branch circuit disconnect that is 20 Amp within the sight of the condenser
unit. The installer should supply the power wiring for the purpose of condensing unit. In any case,
the power wiring should have a minimum of 20 Am circuit Ampacity, and it should be run
through a rain-tight conduit. The condensing unit should be grounded as per the applicable codes.
\
f
\
b
??
???\
f
7.5 The P/N 4028607 Supply Duct Kit
8.Condenser
Setup
8.1A
Location
The
condensing
unit
is
designed
to
be
installed
outdoors
in
a
space
that
is
protected from extreme
weather
(
rain
,
wind
,
etc
.).
Do
not
place
the
condensing
unit
in
direct sunlight
.
•
Place
the
condensing
unit
at
least
1
"
above
ground level
.
Place
the
condensing
unit
as
close
as
possible
to
the
dehumidifer
to
minimize
the
length
of
the
connecting lines
.
The
maximum
line
set
length
is
50
feet
.
•
•
Ensure the mounting of the condensing unit can withstand strong winds and earthquakes when
mounting above ground level
.
•
The
condensing
unit
may
be
mounted
to
a
wall
(
with
brackets
)
or
placed
on
a
roof
.
•
Mount
the
base
of
the
condensing
unit
to
a
sturdy
level
pad
(
or
bracket
)
using
3
/
8"
(
10mm
)
bolts
.
Avoid
directing the discharge
air
at
people
.
•
If
used
near
a
water
source
;
be certain there is no chance the dehumidifer could fall into the water or
get splashed and that it meets NEC standards
.
•
DO NOT
use
the
condensing
unit
as
a
bench
or
table
.
•
Do
not
place
the
condensing
unit
where the sound and vibration caused by running the unit will a
cause a nuisance
.
Vibration
dampening
material
may
be
installed
between
the
condensing
unit
base
and
the
mounting pad if required
.
•
Allow sufcient clearance to handle the unit’s overall dimensions
.
Place the condensing unit where there is adequate space for the unit and the air required by the unit
.
Install
the
condensing
unit
with
space
to
access
the
top
and
side
panels
for
maintenance
and
service
.
•
•
•
8.2 The Procedure of Field Wiring the Condensing Unit
First of all, take off the top panel, by simply removing the screw present on the dehumidifier
securing the condensing unit.
•
Second, loosen the two-strain relief bloc screws.
•
Insert the control and power wires via the strain relief block.
•
Forth, connect the control wires and the power supply wires to the matching terminals on the
terminals board.
•
Make sure you ground the condensing unit with the observance of the national and local
electrical codes.
•
Ensure that you secure the control and power wires to the strain relief block by simply tightening
the available screws.
•
Lastly, reinstall the top panel by inserting the screw that secures the condensing unit.
•
8.3 The Line Set
You should ensure that the lines are perfect for use with the R410a.
You should never crush the line sets and ensure that you may only allow an average bend
radius of 2 inches.
Ensure that the ends of the line sets are well-covered to avoid debris and dirt from
penetrating the lines during the installation process.
Secure the lines nearer to the structure using the isolating hardware to avoid any chances
of vibration transmission to the entire building.
Isolate and seal the openings where the line are routed into the building.
Make sure you insulate the suction (gas) line set to prevent chances of water condensation
occurring within the suction line.
Ensure that you fully flush the line sets with an inert gas prior to and/or during the brazing
process to prevent chances of oxidation occurring in the line sets.
Ensure that you release the inert gas while holding the charge and also remove the plugs
connecting to the dehumidifier lines prior to brazing.
You should never overheat the line sets connected to the device or the condensing unit
during the brazing process.
You should be aware of the most appropriate locations of the condensing (outdoor unit) and
the dehumidifier (indoor unit) when installing the lines.
•
•
•
•
•
•
•
•
•
•