Control valve testing:   

 

Once filled with water, and before use, or if the system has been drained down for a period of time, it is 
important to check the operation of the valve – switch on the control panel and set the temperature to a high 
level (temperature altered by raising the set point). This is done by: 
 

 

press 

 which is too the right of the temperature display. 

 

The lower display will then show “SP” and the upper display will show the actual set point. 

 

Press  

 or 

 to change the set point to the required value. 

 

Finally, press 

 to return to normal run mode. 

 
 
The actuator should slowly rotate clock wise until the valve is at the “2  O’clock” position and then stop. Now 
lower the temperature (below ambient), and the actuator should rotate anti-clockwise and stop at around the 
“10  O’Clock” position. If the actuator does not move, or does not turn full travel, then switch off at the panel by 
turning the isolation knob in the panel door. Pull out central knob of actuator slightly (this exposes orange 
sleeve) – this frees the actuator drive from the valve – then rotate the knob from left to right (or right to left – 
depending upon where the valve is positioned). The valve stem should rotate for about 90 degrees before 
coming to a stop. The valve stem should move relatively easily. If the stem still cannot be rotated, then valve 
has seized. Remove actuator and spray WD40 into where the valve stem goes through the valve body and 
then try rotating valve using a suitable wrench on the end of the stem.. If still no movement, then contact the 
Sales Office. 
 
Re-setting actuator – the central knob can only be pushed back in when the valve and the actuator are exactly 
in line – the valve has be rotated back to the same position it was in before the central knob was pulled out. If 
this proves to be troublesome, remove actuator by un-screwing central set screw in the middle of the actuator 
knob, switch on the panel, set temperature high to force the control system to rotate actuator to fully open 
position, rotate valve to fully open position, install actuator and tighten screw (NOTE – ensure that the back of 
the actuator locks into the locating dowel protruding from the valve body) and then tighten the central screw. 
It should then be possible to push back in the central knob and so covering the orange sleeve. Once done, 
return the control temperature back to the desired value. 
 
 
 

Instantaneous Hot Water Systems 

 
 
1. Installation  
 
Lifting: 

  

Exercise extreme caution at all times when lifting 

 
Do not lift with the secondary shunt pump attached. 

 

Lift from underneath if still on a base (pallet). 

 

Lift off pallet using the lifting hole on the top at the plate heat exchanger (UKE14 only), or by attaching slings 
under or through the base plate – ensure unit is steadied during manoeuvring. It is possible to lift from the top 
frame bar of the heat exchanger (UKE14 only) to steady the assembly – however, do not lift from the frame bar 
without using the lifting hole / from the base,  as well.  
 

 

 

It is also possible to attach a strap or sling around the top flanged connection pipe at F1 location (goes out to 
the control valve) for steadying purposes only – do not lift from this point – use only to steady the unit whilst 
lifting from other areas. 

Содержание UKE-8-50

Страница 1: ...d use of the equipment Important Notice UK Exchangers Ltd cannot accept any warranty claims if the equipment is not handled positioned installed or operated as per the general guide lines contained within this manual The actual running conditions should be checked against the specification sheets for the heat exchanger ...

Страница 2: ...me clock that is incorporated into the panel or Building Management System interface signals During control times schedules the pump s run continuously When in AUTO control by either BMS or time clock only the operation of the pump s is controlled The high temperature over heat protection and the control of the modulating valve is independent of the auto pump control operation Four port valves are...

Страница 3: ... 3 ...

Страница 4: ...upon where the valve is positioned whilst continuing to hold the slide button forward releasing the button locks the actuator drive back to the stem thus preventing manual rotation The valve stem should rotate for about 90 degrees before coming to a stop The valve stem should move relatively easily if not then check that slide button is being pushed forward enough and try again If the stem still c...

Страница 5: ...movement then contact the Sales Office Re setting actuator the central knob can only be pushed back in when the valve and the actuator are exactly in line the valve has be rotated back to the same position it was in before the central knob was pulled out If this proves to be troublesome remove actuator by un screwing central set screw in the middle of the actuator knob switch on the panel set temp...

Страница 6: ...idered positioned local to the exchanger with no control or isolating valves between the device and the exchanger to block the pressure path Welding Do not weld near to or on the heat exchanger or associated components Primary Shunt Pumps The pumps rely on water for cooling and lubrication Damage will be caused if the pumps are run on a dry system DHW Shunt Pump If a DHW pump is supplied loose the...

Страница 7: ... 500 mm away from the exchanger and the over heat located just after the control sensor Route and clip the wires as necessary do not attach any wires near or onto the tie bolts or along the length of the top horizontal frame bar of the heat exchanger Temperature sensors wires Wires to both the sensor and the over heat stat can be extended they are not any special wires 2 core flex for the sensor a...

Страница 8: ...cted to the pump only after the pump has been fitted to the pipe work All other wiring is carried out at the factory All wiring must be carried out by suitably qualified personnel in line with current regulations Panel enclosure IP 65 takes 240 volts or 415 volts if UKE 19 Controller IP 54 Actuator reduced to 24 Volts cover IP41 rated Pump terminal box IP44 rating takes full supply voltage from th...

Страница 9: ... 9 ...

Страница 10: ...t Press or to change the set point to the required value Finally press to return to normal run mode 5 The time clock not fitted on BMS controlled panels is factory set to the correct day and time Should this need alteration this can be done by pressing and holding the CLOCK key whilst pressing the DAY HOUR or MIN keys until the correct values are shown The time clock if fitted is also factory set ...

Страница 11: ...tion valves and drain heat exchanger Tools Ratchet spanners and ring or open ended spanners plus light machine oil M24 36mm across flats Procedure Ensure the control panel is isolated and all isolation valves on the pipe work are closed Allow unit to cool and drain exchanger Release all pressure from inside of exchanger Lightly oil the tie bolt threads down either side of the exchanger Undo the cl...

Страница 12: ...correct see illustration below for herringbone pattern example Assembly diagrams 6 Tightening of the plate pack Procedure Lightly oil tie bolt threads Evenly tighten all bolts We recommend the use of ratchet friction spanners Ensure clamping is as uniform as possible thus keeping the frames plates parallel throughout the operation Avoid skewing the frame plates by more than 10mm Tightening is comp...

Страница 13: ... 13 Examples of Gasket and Plate types ...

Страница 14: ...askets leaking check replace Crack in weld at joint Dye Pen Check and repair remove plates out of heat exchanger before welding 2 cross contamination Check all plates for cracks and or holes 3 leakage from plate pack Check tightening dimension Check condition of the gaskets Check that all gaskets are seated correctly For nearly all leakage problems it is necessary to dismantle the plate pack befor...

Страница 15: ...t on controller b Air Lock in pipe work c Primary water temperature too high or too low d Primary water flow too high too low or secondary flow not correct e Fault in temperature sensor f Actuator fault the valve does not modulate or move during operation g Control valve seized or binding h Primary circuit pressure feeding PHE too high Remedies a Adjust Controller see relevant section in manual b ...

Страница 16: ...dle is binding against the valve body then the paddle then any proud high points can be shaved down by the use of wet and dry or emery paper A possible remedy without taking out valve inners may be to spray lubricant such as WD40 onto valve shaft bearing see section on control valve in Section 1 at beginning of manual and then locate the stem a few times to work in the lubricant If the pressure of...

Страница 17: ...actuator should move until stops at fully closed position Then alter the control Set Point to a high temperature actuator should move to fully open position If all OK then re set control temperature to desired value 8 Maintenance Time interval Once a year as a minimum Performance Check temperatures and flows against commissioning data Plate pack Check the tightening dimension and look for any sign...

Страница 18: ...Type Process High Alarm Process Low Alarm Deviation Alarm Band Alarm No alarm High Alarm 1 value Range Minimum to Range Maximum in display units Range Max Low Alarm 1 value Range Min Band Alarm 1 value 1 LSD to span from setpoint in display units Dev Alarm 1 value Span from setpoint in display units Alarm 1 Hysteresis 1 LSD to full span in display units Alarm 2 Type Options as for alarm 1 High Ala...

Страница 19: ...it 0 to 100 of full power Output 1 Cycle Time 0 5 1 2 4 8 16 32 64 128 256 or 512 secs Output 2 Cycle Time Output 3 Cycle Time High Alarm 1 value Range Minimum to Range Maximum R max Low Alarm 1 value R min Deviation Alarm 1 Value Span from SP in display units Band Alarm 1 value 1 LSD to span from setpoint Alarm 1 Hysteresis 1 LSD to full span in display units High Alarm 2 value Range Minimum to R...

Страница 20: ... Option A module fault or RSP in both A B Option B Error Option B module fault OPERATOR MODE This mode is entered at power on or accessed from Select mode see section 2 Note All Configuration mode and Setup mode parameters must be set as required before starting normal operations Press to scroll through the parameters then press or to set the required value Note All Operator Mode parameters in Dis...

Отзывы: