30
103626-04 - 3/18
VIII. SYSTEM START-UP (continued)
4. FLAME FAILURE
The LE boiler controls operate the burner
automatically. If for unknown reasons the burner
ceases to fire and the reset button on the primary
control has tripped, the burner has experienced
ignition failure. Refer to Oil Primary Control
features, Paragraph I, Step 2 of this section and
Section XII, Troubleshooting, Paragraph B. If the
failure re-occurs, call your heating contractor
immediately before pressing the reset button.
WARNING
DO NOT attempt to start the burner when excess
oil has accumulated, when the boiler is full of
vapor, or when the combustion chamber is very
hot.
5. CAD CELL LOCATION AND SERVICE
The burner is supplied with a cadmium sulfide flame
detector mounted at the factory, mounted on the
bottom of the electronic ignitor. See Figure 22. To
service cad cell or to replace the plug in portion,
swing open the ignitor. After service is complete, be
sure to fasten down the ignitor.
Figure 22: Cad Cell Location
H.
CHECK FOR CLEAN CUT OFF OF BURNER.
1. AIR IN THE OIL LINE between fuel unit and
nozzle will compress when burner is on and will
expand when burner stops, causing oil to squirt from
nozzle at low pressure as burner slows down and
causing nozzle to drip after burner stops. Usually
cycling the burner operation about 5 to 10 times will
rid oil line of this air.
2. IF NOZZLE CONTINUES TO DRIP, repeat
Paragraph H, Step 1 above. If this does not stop the
dripping, remove cut-off valve and seat, and wipe
both with a clean cloth until clean, then replace and
readjust oil pressure. If dripping or after burn
persist replace fuel pump.
I.
TEST CONTROLS.
1. Check thermostat operation. Raise and lower
thermostat setting as required to start and stop
burner.
WARNING
Before installation of the boiler is considered
complete, the operation of all boiler controls must
be checked, particularly the primary control and
high limit control.
2.
VERIFY OIL PRIMARY CONTROL FEA-
TURES
using procedures outlined in Instructions
furnished with control or instructions as follows:
a.
GeniSys 7505 Control Features
, see Figure 23.
i.
The GeniSys 7505 is a microprocessor-based
control. The indicator light provides diagnos-
tic information for lockout, recycling and cad
cell status. There is a manual reset button to
exit the Lockout Mode.
ii.
Pump Priming Cycle: To facilitate purging
air from the oil lines and filters, the 7505 can
be placed in a purge routine by:
• After the burner starts, press and hold the
reset button for 15 seconds until the
yellow light turns on. This indicates that
the button has been held long enough.
• Release the reset button. The yellow light
will turn off and the burner will start up
again.
Figure 23: GeniSys 7505 Oil Primary Terminals,
LED's and Reset Button
Содержание LE Series
Страница 5: ...5 103626 04 3 18 I GENERAL INFORMATION Figure 1A LE Packaged Water Boiler with Beckett AFG Burner...
Страница 46: ...46 103626 04 3 18 XIII REPAIR PARTS continued Figure 27 LE Bare Boiler Assembly...
Страница 48: ...48 103626 04 3 18 XIII REPAIR PARTS continued Figure 28 LE Boiler Jacket Insulation...
Страница 58: ...58 103626 04 3 18...
Страница 59: ...59 103626 04 3 18...
Страница 60: ...60 103626 04 3 18 U S Boiler Company Inc P O Box 3020 Lancaster PA 17604 1 888 432 8887 www usboiler net...