VII. OIL PIPING
A.
GENERAL
1. Use flexible oil line(s) so that burner can be re
-
moved without disconnecting the oil supply.
2. A supply line fuel oil filter is recommended as a
minimum for all firing rates but a pleated paper fuel
oil filter is recommended for the lowest firing rate
application to prevent nozzle fouling.
3. Use Flared fittings only.
DO NOT
use compression
fittings.
4. Use of a high efficiency micron filter (Garber or
equivalent) in addition to conventional filter is
highly recommended.
B.
SINGLE-PIPE OIL LINES
1. Standard burners are provided with single-stage
3450 rpm fuel units with the bypass plug removed
for single-pipe installations.
2. The single-stage fuel unit may be installed single-
pipe with gravity feed or lift. Maximum allowable
lift is 8 feet. See Figure 13.
NOTICE
Oil piping must be absolutely airtight or leaks or
loss of prime may result. Bleed line and fuel unit
completely.
Figure 13: Single-Pipe Installation