28
103626-04 - 3/18
VIII. SYSTEM START-UP (continued)
Figure 18: Riello Electrode Setting
f.
Re-install Drawer Assembly
into Combustion
Head
per Step 3c above.
g.
Insertion Depth,
verify the distance between the
tip of the end cone is equal to the distance
specified in Table 6.
h.
Check
Turbulator and Air Gate Setting
, refer
to Figure 19 and Riello Burner Specifications
Table 6.
Figure 19: Riello Turbulator Setting
i.
Pump Connections and Port Identification
,
refer to Figure 20.
This burner is shipped with the oil pump set to
operate on a
single
line system. To operate on a
two-line
system the bypass plug must be
installed.
WARNING
:
DO NOT
operate a
single
line system
with the by-pass plug installed. Operating a
single
line system with the by-pass plug installed
will result in damage to the pump shaft seal.
Note:
Pump pressure was factory pre-set but must
be checked at time of burner start-up. A
pressure gauge is attached to the
PRESSURE/
BLEEDER PORT
(7) for pressure readings.
Two
PIPE CONNECTORS
(4) are supplied
with the burner for connection to either a single
or two-line system. Also supplied are two
ADAPTORS
(3), two female ¼” NPT to adapt
oil lines to burner pipe connectors. All pump
port threads are
British Parallel Thread
design.
Direct connection of NPT threads to the pump
will damage
the pump body.
Riello manometers and vacuum gauges
DO
NOT
require any adapters, and can be safely
connected to the pump ports. An NPT x metric
adapter
must
be used when connecting other
gauge models.
j.
Replace Burner Cover
and Tighten Burner
Cover Screws.
k. OPEN ALL OIL LINE VALVES.
l. Provide a pan to catch oil.
m. Remove pressure port/bleeder plug from fuel
pump and install Riello Combination Pressure
Gauge and Bleeder Valve Assembly.
n. OPEN FLAME OBSERVATION PORT COVER
on burner swing door.
Figure 20: Riello Pump Connections and Port Identification
Содержание LE Series
Страница 5: ...5 103626 04 3 18 I GENERAL INFORMATION Figure 1A LE Packaged Water Boiler with Beckett AFG Burner...
Страница 46: ...46 103626 04 3 18 XIII REPAIR PARTS continued Figure 27 LE Bare Boiler Assembly...
Страница 48: ...48 103626 04 3 18 XIII REPAIR PARTS continued Figure 28 LE Boiler Jacket Insulation...
Страница 58: ...58 103626 04 3 18...
Страница 59: ...59 103626 04 3 18...
Страница 60: ...60 103626 04 3 18 U S Boiler Company Inc P O Box 3020 Lancaster PA 17604 1 888 432 8887 www usboiler net...