35
Figure 26: Intelligent Oil Boiler Control -
Horizontal mount Shown
IX. OPERATING
A.
WATER BOILERS SEQUENCE OF OPERATION
1.
Water Boilers Without Tankless Heaters
(Cold
Start), Sequence Of Operation:
a. The LEDV Boiler is equipped with an Intelligent
Oil Boiler Control (cold start boiler control).
The boiler control replaces the traditional
electronic aquastat and circulator relays and adds
energy saving thermal purge features. Energy is
saved by starting the circulator and delaying the
burner start when there is residual heat available
in the boiler.
b. The boiler’s sequence of operation is shown as
Status Codes on Boiler Control display. See
Table 8 and Figure 26.
Status Codes Displayed in
Mode
Status
Description
Standby
(burner off,
pump off)
No call for heat detected
Standby
(burner off,
pump on)
Either condition is true:
a. Call for heat detected and boiler
temperature higher than operating
setpoint.
b. Call for heat detected and boiler
temperature higher than 140 F and
Pump Pre-Purge Time has not
expired.
Running
The burner runs until the call for heat is
satisfied.
Self Test
Control internal checking
TABLE 8: SEqUENCE OF OPERATION
2.
Using Boiler Control
The Boiler Control is located on front of boiler.
The Boiler Control display, along with Up
ñ
,
Down
ò
,
and
“
I
”
keys may be used to view boiler
operating status (Figure 27).
3.
Viewing the Operating Mode Options
In operating mode the user may view (but not
change) boiler operating status, settings and
troubleshooting information. To view Boiler
Control display information:
Figure 27: Boiler Control
Key Function & Orientation
c. When the thermostat calls for heat the boiler
control starts the system circulator and the
thermal purge (circulator pre-purge time) begins.
If the time is completed or boiler temperature is
less than the Start Temperature (140 F default)
the start sequence continues by energizing the oil
primary to operate the following sequence:
blower is started and operates for pre-purge time;
spark is energized and fuel valve is opened for
ignition trial time; burner fires until the
thermostat is satisfied.
d. If the thermostat is not satisfied and the Operat
-
ing Setpoint (SP) is reached the system circulator
will continue to operate and the burner will stop.
When the boiler water temperature drops below
the setpoint less the differential setting the burner
will restart.
e. After the thermostat is satisfied the burner and
circulator are stopped.
f. When an indirect water heater aquastat call for
heat is wired to the “ZR” terminal the Boiler
Control starts a domestic hot water circulator
connected to the “ZC” terminal and when the
boiler temperature is less than Operating Setpoint
(SP), the boiler control energizes the oil primary
to turn on the burner without circulator pre-purge
delay.
g. On burner start, if the CAD cell does not see
flame within approximately 15 seconds, primary
control will shut down the burner and enter into a
lockout mode. A lockout is reset by pressing the
reset button located on the primary control. If
the flame is lost while the burner is firing, the
primary control shuts down the burner, enters a
60 second recycle delay, and repeats the ignition
sequence. If after three (3) trials for ignition,
flame is not detected, primary control will enter
into restricted mode. Restricted mode is reset by
holding down the reset button for 15 seconds.
Содержание LE DV Series
Страница 5: ...5 I General Information Figure 1A LEDV Packaged Water Boiler with Beckett AFII Burner ...
Страница 6: ...6 I General Information continued Figure 1B LEDV Packaged Water Boiler with Riello BF Burner ...
Страница 19: ...19 v venting continued Figure 11 Vent Installation Figure 12 Vent Connector Un Assembled ...
Страница 20: ...20 v venting continued Figure 13 Vent Connector Assembled Figure 14 Air Intake Installation ...
Страница 48: ...48 xiii Repair Parts continued Figure 29 LEDV Bare Boiler Assembly ...
Страница 50: ...50 xiii Repair Parts continued Figure 30 LEDV Boiler Jacket Insulation ...
Страница 55: ...55 xiii Repair Parts continued Figure 33 Vent Kit Repair Parts ...
Страница 60: ...60 U S Boiler Company Inc P O Box 3020 Lancaster PA 17604 1 888 432 8887 www usboiler net ...