Document: LT0273
MX4428 MXP Engineering / Technical Manual
Device Information and Programming
Issue 1.5
24 March 2006
Page 3-41
DIM800 DETECTOR
INPUT MONITOR
L+
L+
L-
L-
NEXT
DEVICE
PREVIOUS
DEVICE
ANALOG LOOP
ANALOG LOOP
A+ A- B+ B-
+
24V
CO
M
EXT
PSU
+
-
4k7 EOL
4k7 EOL
Conventional
Detectors
(refer appropriate
wiring diagrams)
Refer text for
voltage
requirements
Unused inputs (A or B) must be
terminated with 4k7 EOL.
Figure 3.6 DIM800 Field Wiring
3.20.2 DIM800
SPECIFICATIONS
Dimensions
Height: 61mm Width: 84mm Depth: 25mm
Weight 100g
Line Connections
L-, L+
Loop Supply Voltage
20V – 40V
Loop Supply Current
Standby/Alarm Loop Current : 100uA (typical)
EOL
4k7 + / - 1%.
Detector Load
3.0mA max per circuit
External Current (normal)
7.5mA (excluding detectors)
External Current (shorted)
30 - 50mA (depends on supply voltage)
External Supply Voltage
Refer to Table 3-4 for each detector.
Maximum Line Resistance
50
Ω
(with detectors)
1750
Ω
(with hard contacts only)
Short Circuit Fault Option
Maximum line resistance 34
Ω
Minimum Detector Alarm Voltage 5.0V