MX4428 MXP Engineering / Technical Manual
Document: LT0273
Device Information and Programming
Page 3-2
24 March 2006
Issue 1.5
3.1
DEVICE TYPES
The MXP can communicate with a mix of up to 200 addressable devices, within limits
defined by loop size.
3.1.1 MX
DEVICES
MX devices fall into three basic types:
(a)
Sensors
-
Detectors (814PH, 814CH, 814I, 814H, VLC800)
(b)
Ancillaries
-
Input (Monitor) (MIM800, MIM801, CIM800, DIM800)
-
MCP (CP820, FP0838, FP0839)
-
Output (Control) (RIM800, SNM800, LPS800)
(c)
Bases
-
Standard Base (MUB, 5B)
-
Short Circuit Isolator (5BI)
-
Relay Base (814RB)
-
Sounder Base (814SB, MkII Sounder Base)
In addition non-addressable smoke, thermal or flame detectors may be connected to the
MXP loop by means of the DIM800 Detector Input Module.
Code Description
Input
/
Output
Remote
LED
814PH
Photoelectric Smoke + Heat Detector I/O
Y
814CH
Carbon Mo Heat Detector
I/O
Y
814I Ionisation
Smoke
Detector
I/O
Y
814H Heat
Detector
I/O Y
VLC800
Vesda Aspirating smoke detector
I/O
Y
MIM800
Mini Input Module
Input
MIM801
Mini Input Module normally closed
interrupt (FP0837)
Input
CP820
Manual Call Point
Input
FP0838
FP0839
NZ Manual Call Point
Input
CIM800
Contact Input Module
Input
DIM800
Detector Input Module
Input
RIM800
Relay Interface Module (unsupervised
load wiring)
Output
SNM800
Sounder Notification Module (relay
output with supervised load wiring)
Output
LPS800 Loop
Powered
Sounder Output
The devices above are addressed by the
801AP Service
Tool
or by command from the diagnostics terminal of an MXP.