![Tyco 3G4000W Скачать руководство пользователя страница 6](http://html1.mh-extra.com/html/tyco/3g4000w/3g4000w_installation-manual_1185953006.webp)
Installing the 3G4000W
Step 1 – Activate SIM card
The 3G4000W cellular alarm communicator requires a data only SIM card in 3FF Micro size. It is recommended that the SIM card
be activated with an appropriate data and billing plan prior to installing the communicator.
Step 2 - Determine the Best Signal Location
1. Remove the front cover by inserting a screwdriver into each of the slots at the bottom of the enclosure and pushing down.
2. Apply power (DC and/or battery). The 3G4000W will indicate signal strength after successfully registering on the 2G or 3G cellular
network.
Step 2a – SIM Card is activated
The red LED will be on solid, the blue LED will be off and the signal strength LEDs will display the average signal
strength. In this state, the 3G4000W is registered to the cellular network.
If the signal strength is too low (bottom signal LED off or flashing), the 3G4000W will move to
Step 3
and scan for carriers
with sufficient signal strength. If the 3G4000W is connected to a carrier with sufficient signal strength (minimum of bottom
signal strength LED on solid), it will move to
Step 4
.
Step 2b – SIM Card is not yet activated
The red LED will flash, the blue LED will be off and the signal strength LEDs will display the average signal strength.
In this state, the 3G4000W is unable to register to the cellular network because it is inactive. The signal strength indicated
is from
any
nearby cell tower (including cellular towers belonging to non-roaming partners) and does
not
necessarily
reflect the signal strength of the intended network. The 3G4000W will remain in this state until the SIM is activated. Once
the SIM is activated, the communicator will move to
Step 2a
.
Step 3 – Carrier Scanning Due To Insufficient Signal Strength
The 3G4000W will scan the surrounding cellular network and connect to the carrier. When this action is being performed, all four
LEDs will activate to show a scanning sequence. The LEDs will cycle from top to bottom and then bottom to top. This cycle will
continue until the 3G4000W is connected to a carrier with sufficient signal strength
This process can take several minutes.
The carrier scanning sequence repeats until complete.
Step 4 – Create a new account in within the Downloading Software
Open the downloading software. From the Start Page in the DLS software, click on New Account. Enter a name for the account,
and select 3G4000W v5.0 from the Panel Type dropdown box. Select SMS as the connection type, and enter the phone number of
the SIM card.
Note: It is possible to use the account template feature at this stage to quickly load cellular APN, login and password information for
the SIM card, and receiver IPs and Ports so this data doesn’t need to be manually entered for each installation.
With the cover to the enclosure removed, connect a 4 PIN PC-Link adaptor and cable to the PCLINK header on the 3G4000W
circuit board.
Step 5 – Receiver Initialization
Initially, the red LED and the blue LED are both solid and the signal strength LEDs are off.
When the LE4000 sends a request to communicate with the receiver, the top signal strength LED will begin flashing.
When the central station communicates back with the LE4000, the top signal strength LED will turn on solid.
When the LE4000 sends a request to communicate with the next receiver (if programmed), the bottom signal strength LED will
begin flashing.
When a signal is received from the central station, the bottom signal strength LED turns on solid.
If at least one receiver could not be initialized, the signal strength LED corresponding to that receiver will turn off.
Step 6 - Mount the 3G4000W
NOTE:
If using a 3G4000W trim plate, snap the 3G4000S back plate onto the trim plate before mounting to the wall. If flush
mounting or using with an extension antenna, remove the provided breakaway from the trim plate prior to mounting.
1. Using the mounting holes on the LE4000 backplate, mark the four screw locations. Drill the anchor screw holes. NOTE:
Check for cable conduits and water pipes before drilling.
2. Inspect the mounting surface. Ensure that the surface is flat and will hold the wall tamper closed when mounted. Using anchor
screws (not provided), mount the cabinet to the wall. If the tamper cannot be secured it can be disabled via a programmable option.
3. Run the cables through the cable entry [13] or through the cabinet cable run knockout [15].
4. Complete the connections on the terminal blocks [12].