26
Figure 8-4 Alarm Control Unit and 3G Transmitter
Alarm
Control
Unit
Zone
Inputs
TIP
RING
PGM
Keypad
LTE Wireless
Communicator
LE4000
T1/R1
TIP/RING
Zone
Input
PGM2
AUX Power
12V/500mA
RM1C ULC
Relay
LTE/3G
PSTN
AC Input
RM1C ULC
Relay
LE4000 cabinet
NOTES
:
1. Power for LE4000 must be provided from Alarm
Control Unit or separately listed power supply rated
for the application (12V/500mA).
2. Phone Line Monitoring (TLM) must be enabled.
3. Phone Line trouble is indicated by blue LED on
LE4000.
4. Connect PGM2 output from LE4000 (Trouble
Conditions) to a zone input on the Alarm Control
Unit for supervision of the Transmitter.
5. 24hr Test Transmission over phone line (PSTN) and
LE4000 must be enabled.
6. Connect an output (PGM) from Alarm Control
panel to an input on the LE4000 to monitor the
T1/R1 connection.
LE4000 Installation Manual