4.4 Installing the System using the 4-Post Rack Kit
!
WARNING:
Due to the weight of the system, two people are required to lift and mount
the system into a rack enclosure when following the procedure.
Remove all compute blades from the chassis. Refer to
Removing a Compute
Blade
.
Remove the Pass-through-M1902F65-CMMPT module. Refer to
Removing Pass-
through-M1902F65-CMMPT
.
Remove the power supply modules. Refer to
Removing a Power Supply
Module
.
Prerequisite:
1. Lift the chassis until it is leveled with the outer rails on the rack. (Figure 2-12)
2. Align the left and right side of the inner rail on the chassis with the outer rails
on the rack.
3. Insert the rear side of the chassis into the rack until the inner rails and outer
rails lock into place.
4. Secure the chassis to the rack by installing (2) screws from the mounting
flanges to the rail.
5. Install the compute blades into the chassis. Refer to
Installing a Compute
Blade
.
!
CAUTION
:
Compute blades should be installed in the order shown in
Compute Blade, Power
Supply & Fan Module Order Identification
.
6. Install the Pass-through-M1902F65-CMMPT module into the chassis. Refer to
Installing
Pass-through-M1902F65-CMMPT Module
.
7. Install the power supply modules. Refer to
Installing a Power Supply Module
.
Outer Rail
Inner Rail
Figure 2-12. Installing the System to a 4-Post Rack