THERMOSTAT MODEL TD-196 OPERATING MANUAL
SPECIFICATIONS TD-196 CONT. :-
ALARMS SET POINT
RESOLUTION
:-
0.1 oC.
ALARM DELAY SET RANGE
(HI & LO)
:-
0 - 120 minutes.
(1 on each channel).
ALARMS DELAY SET
RESOLUTION
:-
1 minute.
ALARM
(INTERNAL)
:-
pulsed visual and audio.
ALARM OUTPUT
:-
dry relay output,
rated 24 V d.c. 1 A.
DEFROST MANUAL SET RANGE
:-
1 min - 120 min.
DEFROST AUTOMATIC SET
RANGE
:-
1 min - 60 min.
DEFROST SOL. TURN ON DELAY
RANGE
:-
0 min - 60 min.
FANS & SUCTION ON (FIRST DELAY)
RANGE
:-
YES or NO
DEFROST REF. TURN ON DELAY
RANGE
:-
0 min - 10 min.
DEFROST FANS TURN ON DELAY
RANGE
:-
0 min - 10 min.
DEFROST HOLD OFF DELAY
RANGE
:-
0 min - 30 min.
(holds alarms & max.
min from updating.)
NUMBER OF DEFROSTS PER DAY :-
8
DEFROST START TIMES
:-
ANY MINUTE OF THE DAY
DEFROST MANUAL
:-
ON - OFF may be activated at any time.
DEFROST AUTOMATIC
:-
AUTO - OFF may be
activated or deactivated.
MAXIMUM MINIMUM
:-
max. & min of channels temp & at what
time it occurred in DATE then HOUR.
REAL TIME CLOCK
REAL TIME CLOCK CALIBRATION:-
+30 to -30. 1 count = 5.34 seconds per
month.
NOTE :- 240V AC IS APPLICABLE TO COUNTRIES WITH THAT POWER
SUPPLY, OTHER COUNTRIES WITH DIFFERENT POWER SUP
PLIES ADJUST ACCORDINGLY.
Содержание TD-196
Страница 39: ...39 TWITE INSTRUMENTS THERMOSTAT MODEL TD 196 OPERATING MANUAL SETTING FUNCTIONS CONT...
Страница 42: ...42 TWITE INSTRUMENTS THERMOSTAT MODEL TD 196 OPERATING MANUAL CALIBRATION AND DEFAULT VALUES CONT...
Страница 63: ...63 TWITE INSTRUMENTS THERMOSTAT MODEL TD 196 OPERATING MANUAL NOTES...
Страница 64: ...64 TWITE INSTRUMENTS THERMOSTAT MODEL TD 196 OPERATING MANUAL NOTES...