| FR700V SERIES FUEL TRANSFER PUMPS
TYPICAL PEDESTAL / ISLAND INSTALLATION
CAUTION!
Threaded pipe joints and connections should be sealed with the appropriate sealant or sealant tape to minimize the possibility of leaks.
Typical Skid Tank Installation
Materials
• 1¼" pipe cut to a length that will extend to within 3" of the bottom of the tank
when screwed into the tank adapter with the tank adapter screwed into the tank
flange (see SKID TANK INSTALLATION diagram).
• Threaded pipe joint sealant appropriate for application.
• Anti-seize thread compound.
Installation Procedure
1. Thread the 1¼" pipe into the tank adapter. Seal threads liquid tight with
appropriate thread sealant.
2. Apply an anti-seize thread compound to the external threads on the bottom of
the bung adapter. Screw the tank adapter into the tank flange.
3. Mount the pump on the adapter; seal threads liquid tight with appropriate
thread sealant.
4. Fill-Rite recommends installation of an Anti-Siphon Device
(see page 5 for detailed information).
Typical "Island" Installation
Materials
• 1¼" threaded suction pipe, cut to extend 32-1/2" above the island.
• FRPA125 Pedestal Kit (includes Pedestal Pipe, Base, & Coupler).
• Threaded pipe joint sealant appropriate for application.
Installation Procedure
1. Remove the coupler from the pedestal pipe by loosening the set screws.
2. Slip the pedestal pipe / pump base assembly over the 1¼" suction pipe.
3. Loosen the screws in the pump base to allow the pedestal pipe to slide down
exposing the end of the suction pipe.
4. Screw the coupler onto the suction pipe; seal threads liquid tight with
appropriate thread sealant.
5. Slide the pedestal pipe into the coupler and tighten the set screws.
6. Tighten the screws in the pump base.
7. Mount the pump on the coupler seal threads liquid tight with appropriate
thread sealant.
LAYOUT OF BASE ANCHOR BOLTS
PUMP FRONT
1/2" BOLTS
1-7/8"
1-7/8"
ELECTRICAL CONDUIT
CLEARANCE HOLE
7 25/32"
SKID TANK INSTALLATION
PEDESTAL COUPLER
PEDESTAL PIPE
PEDESTAL BASE
FUEL TANK
1¼" SUCTION PIPE
ELECTRICAL CONDUIT
CONCRETE ISLAND
36" SQUARE
3" MIN. OFF
TANK BOTTOM
Additional specifications
on page 7.
Additional
specifications on page 7.
TANK ADAPTER
SKID TANK
Содержание FILL-RITE FR700 Series
Страница 1: ...MADE IN USA FR700V SERIES FUEL TRANSFER PUMPS Installation and Operation Manual ...
Страница 13: ...MADE IN USA POMPES DE TRANSFERT DE CARBURANT SÉRIE FR700V Manuel d installation et d utilisation ...
Страница 25: ...MADE IN USA BOMBAS DE TRANSFERENCIA DE COMBUSTIBLE SERIE FR700V Manual de instalación y operación ...
Страница 37: ...MADE IN USA BOMBAS DE TRANSFERÊNCIA DE COMBUSTÍVEL DA SÉRIE FR700V Manual de Instalação e Operação ...
Страница 49: ...СДЕЛАНО В США НАСОСЫ ДЛЯ ПЕРЕКАЧКИ ТОПЛИВА СЕРИЯ FR700V Руководство по установке и эксплуатации ...