U s e r I n s t r u c t i o n s
Eco-Net 128 Control Unit
InMn 26 UCESTD
it Rev.1.02
TURBO s.r.l.
Dust Filter Components
Via Po 33/35 20811 Cesano Maderno (MB) Italy Tel ++39 0362 574024 Fax ++39 0362 574092
21
Setting the pressure thresholds dP
The control unit software has
(*)
a limitation function of the pressure threshold settings regarding the
“dP Start”, “dP Stop” and “dP Fan On/Off” values.
These values contribute to the execution of
the functions relative to the automatic
cleaning and post-cleaning cycles.
As highlighted in the table at the side, the
“dP Start” threshold that can be set, will be
a value between the dP Stop” threshold and
the full scale value (FS).
The “dP Stop” threshold that can be set, will
be a value between the “dP Fan On/Off”
threshold and that of “dP Start”.
The “dP Fan On/Off” threshold that can be
set, will be a value between 0KPa and the
“dP Stop” threshold.
(*) from the SW 7.5 version
Setting the pressure unit of measurement
Through the menu item “Unit Measure dP” of the
Main Set Up
menu, the user can set the pressure unit
of measurement to display among those available on the control unit:
Unit
of measurement
KPa
(**)
millibar
Inch WC mm H2O
Conversion
of the pressure
1
10
101.97
4.014
(**)
default setting
Warning: The selection of a new unit of measurement of the pressure dP DOES NOT lead to automatic
modification of the dP thresholds set in the configuration menu. Therefore, the user must set ALL of the
pressure dP thresholds again, so that they are consistent with the dP unit of measurement selected.