ID551PN
Weighing Controller
22
3.5 MODBUS-RTU2 & MODBUS-TCP2 Data Format
MODBUS-RTU2 & MODBUS-TCP2 – 1# 2#Scale
Register
Description
Operation
40001/2
1# Scale
:
Floating point display weight
R
40003/4
1# Scale
:
gross weight
R
40005
1#Scale Status
Bit 0 – 0(Two point calibration mode) 1
(
CalFree
)
Bit1 - 0
(
Disable Tare
)
1
(
Enable Tare
)
Bit 7 – CalFree Error
Bit 8
– In
Center of Zero
Bit 9
–
Under Zero
Bit 10
–
Over Capacity
Bit 11
–
Net
Bit 12
–
Motion
Bit 13
–
Power Up Zero OK
Bit 14
– Setup Mode
Bit 15
–
Weight Data OK
R
40006
1#Scale Demand
:
Bit 0 – 0-Disable 1-Enable MODBUS remote calibration
Bit 1 - 0
(
Unlock Keypad
)
1(
Lock Keypad)
Bit 11
–
0->1
Trigger Pushbutton Zero
Bit 12
–
0->1
Trigger Pushbutton Tare
Bit 13
–
0->1
Trigger Pushbutton Clear
Bit 14
–
Bit 15
–
0->1
Trigger Scale Re-Init All
R/W
40007/8
2# Scale
:
Floating point display weight
R
40009/10
2# Scale
:
Gross Weight
R
40011
2#Scale Status
Bit 0 – 0(Two point calibration mode) 1
(
CalFree
)
Bit1 - 0
(
Disable Tare
)
1
(
Enable Tare
)
Bit 7 – CalFree Error
Bit 8
– In
Center of Zero
Bit 9
–
Under Zero
Bit 10
–
Over Capacity
Bit 11
–
Net
Bit 12
–
Motion
Bit 13
–
Power Up Zero OK
Bit 14
– Setup Mode
Bit 15
–
Weight Data OK
R
40012
2#Scale Demand
:
Bit 0 – 0-Disable 1-Enable MODBUS remote calibration
Bit 1 - 0
(
Unlock Keypad
)
1(
Lock Keypad)
Bit 11
–
0->1
Trigger Pushbutton Zero
Bit 12
–
0->1
Trigger Pushbutton Tare
Bit 13
–
0->1
Trigger Pushbutton Clear
Bit 14
–
Bit 15
–
0->1
Trigger Scale Re-Init All
R/W