2
Configuration
Before you use EM-BAC-MOD as a BACnet or Modbus
interface module, you have to configure it to the actual
application. To do so, use the switches on the interface
module.
Fig. 1: EM-BAC-MOD
①
Switch to select BACnet MS/TP or Modbus RTU
protocol
②
Switches to set the network addresses, 01-99
③
DIP switch to set communication parameters
Setting the protocol type
1.
Use the slide switch
①
to set the BACnet MS/TP
or Modbus RTU protocol.
Setting the network address
2.
Use the two address code switches X and Y
②
to
set a network address (01 to 99). Address 00 is
reserved for broadcast mode.
A maximum of 32 devices (network addresses)
can be operated on one network segment.
Cau-
tion:
a different network address must be set for
every device.
Setting the device family
3.
If the device is to be used with an EASYLAB/
TROX UNIVERSAL controller or a adapter module
TAM, use the DIP switch
③
to set switch S1 to
Off.
Communication parameters
4.
Use the DIP switch
③
to set the following parame-
ters:
S2 + S3 - Transmission speed EIA-485
S5 + S6 - Parity
S8
- Terminal resistor
Ask the responsible specialist consultant for the
values to be set.
Setting the transmission speed for BACnet
BACnet
S2
S3
9600 Bd
Off
Off
19200 Bd
On
Off
38400 Bd
Off
On
76800 Bd
On
On
Setting the transmission speed for Modbus
Modbus
S2
S3
9600 Bd
Off
Off
19200 Bd
On
Off
38400 Bd
Off
On
57600 Bd
On
On
Setting parity
Parity
S5
S6
None
Off
Off
None
On
Off
Odd
Off
On
Even
On
On
Terminal resistor for EIA-485 network from
rev. 2
Terminal resistor
S8
Disabled
Off
Enabled
On
Configuration
Expansion module EM-BAC-MOD-01
7