Configuration switches
Hexadecimal Switches X, Y
Network address
DIP Switch 1
OFF
ON
Controller
EASYLAB TCU3
Other
DIP Switch 2
OFF
ON
OFF
ON
DIP Switch 3
OFF
OFF
ON
ON
Baud rate
9600
19200
38400
76800
BIBBS - BACnet Interoperability Building Blocks Supported
Data Sharing-ReadProperty-B
DS-RP-B
Data Sharing-WriteProperty-B
DS-WP-B
Data Sharing-COV-Unsolicited-B
DS-COVU-B
Device Management-Dynamic Device Binding-B
DM-DDB-B
Device Management-Dynamic Object Binding-B
DM-DOB-B
Device Management-Device Communication Control-B
DM-DCC-B
Device Management-ReinitialiseDevice-B
DM-RD-B
DeviceObject
Property
Value
Access
Object identifier
Device instance; default instance = 32900 + set network
address
WR, RD; E
Object name
Default="EM-BACnet"; project-specific description can be
entered, 62 characters max.
WR, RD; E
Object type
Device (8)
RD
System_Status
OPERATIONAL (0)
RD
Vendor_Name
"TROX GmbH"
RD
Vendor_Identifier
329
RD
Model_Name
"EM-BAC-MOD"
RD
Description
Default = “EASYLAB”; description can be entered, 126 char-
acters max.
WR, RD; E
Location
Default = ""; description can be entered, 62 characters max.
WR, RD; E
Firmware_Revision
“4.1” (EASYLAB)
RD
Application_Software_Version
“4.1” (EASYLAB)
RD
Protocol_Version
1
RD
Protocol_Revision
12
RD
Protocol Services Supported
Who-is, who-has, read-property, write-property, device-com-
munication-control, reinitialise-device
RD
Interface information
BACnet interface
Expansion module EM-BAC-MOD-01
10
Содержание EM-BAC-MOD-01
Страница 39: ...Expansion module EM BAC MOD 01 39...