DampPosMax_RS
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the room
supply air controller with the widest open damper
blade
1, 4
Data point
BACnet: Analog Value Object – Instance 17 – value
and event state
Modbus: Register 27 (value) and register 28 (event
state)
DampPosMin_RS
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit:
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the room
supply air controller with the least wide open
damper blade
1, 5
Data point
BACnet: Analog Value Object – Instance 18 – value
and event state
Modbus: Register 29 (value) and register 30 (event
state)
DampPosMax_EC
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
not used
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the room
extract air controller with the widest open damper
blade
1, 4
Data point
BACnet: Analog Value Object – Instance 26 – value
and event state
Modbus: Register 49 (value) and register 50 (event
state)
DampPosMin_EC
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
not used
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the room
extract air controller with the least wide open
damper blade
1, 5
Data point
BACnet: Analog Value Object – Instance 27 – value
and event state
Modbus: Register 51 (value) and register 52 (event
state)