4.2  Modbus interface

Application

The expansion module EM-BAC-MOD supports the fol-

lowing Modbus interface functions in the Modbus pro-

tocol settings:

Modbus is an open serial master-slave communica-

tion protocol which has become a de facto standard

for the industry

The master (e.g. central BMS) can address a

number of slaves (EASYLAB volume flow control-

lers) and use Modbus functions to request informa-

tion from individual data points

Data access is based on numbered data registers

which the master has to define in order to request

data using Modbus functions

The slave responds by either returning the

requested information or an exception code (error)

Example: The 

Read Holding Registers

 func-

tion (register no. 3) returns the volume flow rate

actual value of the addressed controller

General information for a Modbus device can be

read out using the 

Read Device

Identifikation

 function

Abbreviations

EASYLAB:

FH

- Fume cupboard controller

RR

- Room controller for supply air or extract air

(RS, RE, PC)

RR RMF - Room controller with active room manage-

ment function

EC, SC

- Single controller for supply air or extract air

(EC, SC)

TAM

- Adapter module

TAM

RMF

- Adapter module with active room manage-

ment function

WR

- Defaults for the volume flow controller or

room, from the central BMS

RD

- Data provided by the volume flow con-

troller or room

TROX UNIVERSAL CONTROLLER:

RS/RE

- Volume flow controllers for supply or

extract air

RS/RE

RMF

- Volume flow controller with active room

management function

PR*/PD*

- Room pressure controller or duct for

supply or extract air

PR*/PD*

RMF

- Room pressure controller or duct with

active room management function

Modbus functions

Function no.

Designation

Meaning

1 (0x01)

Read Coils

Read states of 1 to 8 bits according to bit list

3 (0x03)

Read Holding Registers

Read several consecutive registers

4 (0x04)

Read Input Registers

Read several consecutive registers

5 (0x05)

Write Single Coil

Write state of a single bit

6 (0x06)

Write Single Register

Write single register

8 (0x08)

Diagnostics

Check Modbus communication

16 (0x10)

Write Multiple Registers

Write several consecutive registers

43 (0x2B)

Read Device Identification

Read identification data for the device

14 (0x0E)

Read Device Identification

Read identification data for the device

Interface information

Modbus interface  

 

Expansion module EM-BAC-MOD-01

16

Содержание EM-BAC-MOD-01

Страница 1: ...e EM BAC MOD 01 Configuration manual Read the instructions prior to performing any task Description of data points for BACnet MS TP or Modbus RTU interface for EASYLAB TROX UNIVERSAL Firmware from 4 1...

Страница 2: ...en TROX GmbH 2017 TROX GmbH Heinrich Trox Platz 47504 Neukirchen Vluyn Germany Telephone 49 2845 202 0 Fax 49 2845 202 265 email trox trox de Internet http www troxtechnik com 06 2019 Expansion modul...

Страница 3: ...of the art and our expertise and experience of many years The manufacturer does not accept any liability for dam ages resulting from Non compliance with this manual Incorrect use Operation or handling...

Страница 4: ...ty 6 1 6 Qualified staff 6 1 7 Environmental protection 6 2 Configuration 7 3 Commissioning 8 3 1 Required TCU3 software version 8 4 Interface information 9 4 1 BACnet interface 9 4 2 Modbus interface...

Страница 5: ...entially explosive atmospheres Residual risks Failure of the network interface does not affect the con trol function of the volume flow controller but does affect data exchange with the central BMS Sa...

Страница 6: ...lations for safety accident prevention and environmental protection must also be complied with 1 6 Qualified staff Qualification The work described in this manual has to be carried out by individuals...

Страница 7: ...rent network address must be set for every device Setting the device family 3 If the device is to be used with an EASYLAB TROX UNIVERSAL controller or a adapter module TAM use the DIP switch to set sw...

Страница 8: ...Software version 8 0 or higher TROX UNIVERSAL CONTROLLER Software version 2 1 or higher The software version is displayed in the EasyConnect software Diagnosis Basic Device line A product sticker on t...

Страница 9: ...on WR Defaults for the volume flow controller or room from the central BMS RD Data provided by the volume flow con troller or room TROX UNIVERSAL CONTROLLER RS RE Volume flow controllers for supply or...

Страница 10: ...Value Access Object identifier Device instance default instance 32900 set network address WR RD E Object name Default EM BACnet project specific description can be entered 62 characters max WR RD E Ob...

Страница 11: ...7 WR RD E Max_Info_Frames Default 1 WR RD E Multistate Value Objects In stanc e Description Unit Acc ess Sup port COV TCU3 TAM TROX UNIVERSAL Available with equipment function FH RR RR RMF EC SC TAM T...

Страница 12: ...N 7 VelocitySet m s 74 x RD N 8 VelocityAct m s 74 x RD N 9 WireSen sorPos 98 x RD N 10 DampPos 98 x x x x x x x x RD N 11 Damp PosMax_FH 98 x x x x x x RD N 12 Damp PosMin_FH 98 x x x x x x RD N 13...

Страница 13: ...used 25 SC_GetPos 98 not used 26 Damp PosMax_EC 98 x x x x x x RD N 27 Damp PosMin_EC 98 x x x x x x RD N 28 Damp PosMax_SC 98 x x x x x x RD N 29 Damp PosMin_SC 98 x x x x x x RD N 30 Damp PosMax_TS...

Страница 14: ...x x x x x RD 10 DI5 x x x x x x x x x x RD 11 DI6 x x x x x x x x x x RD 12 DO1 x x x x x x x x x x RD 13 DO2 x x x x x x x x x x RD 14 DO3 x x x x x x x x x x RD 15 DO4 x x x x x x x x x x RD 16 DO5...

Страница 15: ...x x x x x x x RD 26 DO2_SetBy Local x x x x x x x x x x RD 27 DO3_SetBy Local x x x x x x x x x x RD 28 DO4_SetBy Local x x x x x x x x x x RD 29 DO5_SetBy Local x x x x x x x x x x RD 30 DO6_SetBy L...

Страница 16: ...EC SC Single controller for supply air or extract air EC SC TAM Adapter module TAM RMF Adapter module with active room manage ment function WR Defaults for the volume flow controller or room from the...

Страница 17: ...PR PD PR PD RMF 0 Mode x1 x x x x WR N 1 ManOP_Disable x1 x x x x WR N 2 ModeAct x x x x x x RD N 3 VolflowAct x x x x x x x x RD N 4 VolflowSet x x x x x x RD N 5 VelocityAct x RD N 6 VelocitySet x R...

Страница 18: ...x x x x x RD N 24 Damp PosMax_TE Status x x x x x x x x x x RD N 25 Damp PosMin_TE Value x x x x x x x x x x RD N 26 Damp PosMin_TE Status x x x x x x x x x x RD N 27 Damp PosMax_RS Value x x x x x x...

Страница 19: ...ot used 44 SC_GetLockHigh Prio not used 45 SC_SetPos Value not used 46 SC_SetPos Status not used 47 SC_GetPos not used 48 SC_Alarm not used 49 DampPosMax_EC Value x x x x x x RD N 50 DampPosMax_EC Sta...

Страница 20: ...60 DampPosMin_TS Status x x x x x x x x x x RD N 61 DO_Set x x x x x x x x x x WR N 62 DO_SetByLocal x x x x x x x x x x RD N 63 VolflowSet_R x x WR RD N 64 PressSet_R x x WR RD N 65 Volt_AI2 x x x x...

Страница 21: ...nalogue Value Object Function and special functional values with their meaning Access to the data point using a BACnet object or Modbus register TROX UNIVERSAL CONTROLLER RS RE Volume flow controllers...

Страница 22: ...cy 5 4 Shut off Shut off of the volume flow controller e g to save energy at night or to shut down the system 6 5 OPEN position Open position of the volume flow controller Data point BACnet Multistate...

Страница 23: ...ered for all volume flow calculations balance and setpoint values Data point BACnet Analog Value Object Instance 22 Modbus Register 41 VolflowSup BMS access WR RD Equipment function EASYLAB FH RR RR w...

Страница 24: ...RMF TAM with RMF TROX UNIVERSAL RE RS with RMF PR PD with RMF Function Enabling disabling manual control Upon enabling manual control the corresponding symbol appears on the control panel For further...

Страница 25: ...e 5 Modbus Bit list bit 1 or register 13 DO _Set BACnet DO_Set Modbus BMS access WR RD Equipment function EASYLAB FH RR RR with RMF EC SC TAM TAM with RMF TROX UNIVERSAL RE RS RE RS with RMF PR PD PR...

Страница 26: ...yte 20 Obj Length 23 Byte 21 43 Obj Value EM BAC MOD EASYLAB Byte 44 ID MajMinRevision 0x02 Byte 45 Obj Length 4 Byte 46 49 Obj Value V3 0 ModeAct BMS access RD Equipment function EASYLAB FH RR RR wit...

Страница 27: ...tep of the fume cup board as a numeric value if the fume cupboard con troller is equipped with switch contacts for 2 point or 3 point control FH2P FH 3P Data point BACnet Multistate Value Object Insta...

Страница 28: ...her controllers Data point BACnet Analog Value Object Instance 3 Modbus Register 7 VolTotalSup BMS access RD Equipment function EASYLAB FH RR RR with RMF EC SC TAM TAM with RMF TROX UNIVERSAL RE RS RE...

Страница 29: ...VelocityAct BMS access RD Equipment function EASYLAB FH TROX UNIVERSAL not used Unit m s Function Output of the face velocity actual value if the fume cupboard controller is equipped with a face veloc...

Страница 30: ...n EASYLAB FH RR RR with RMF EC SC TAM TAM with RMF TROX UNIVERSAL not used Unit V DC Function Output of the voltage at analogue input AI3 0 10 V DC in increments of 0 1 V Data point BACnet Analogue Va...

Страница 31: ...ressure alarm Data point BACnet Binary Value Object Instance 3 Modbus Bit list bit 4 or register 33 DI BACnet StateDI Modbus BMS access RD Equipment function EASYLAB FH RR RR with RMF EC SC TAM TAM wi...

Страница 32: ...alue range BACnet Percentage value in increments of 0 5 Modbus 0 200 200 corresponds to 100 Function Output of the damper blade position of the fume cupboard controller with the widest open damper bla...

Страница 33: ...Register 19 value and register 20 event state DampPosMin_RE BMS access RD Equipment function EASYLAB FH RR RR with RMF EC SC TAM TAM with RMF TROX UNIVERSAL RE RS RE RS with RMF PR PD PR PD with RMF...

Страница 34: ...gister 23 value and register 24 event state DampPosMin_TE BMS access RD Equipment function EASYLAB FH RR RR with RMF EC SC TAM TAM with RMF TROX UNIVERSAL RE RS RE RS with RMF PR PD PR PD with RMF Uni...

Страница 35: ...18 value and event state Modbus Register 29 value and register 30 event state DampPosMax_EC BMS access RD Equipment function EASYLAB FH RR RR with RMF EC SC TAM TAM with RMF TROX UNIVERSAL not used U...

Страница 36: ...ontroller with the least wide open damper blade 1 5 Data point BACnet Analog Value Object Instance 29 value and event state Modbus Register 55 value and register 56 event state DampPosMax_TS BMS acces...

Страница 37: ...rds extract air and room extract air 4 Status information for damper blade positions Damp PosMax_ BACnet Functional value 1 All damper blades in OPEN position special operating mode value 100 Override...

Страница 38: ...nd electronic parts 6 Rechargable batteries 6 H Hotline 3 I Incorrect use 5 Interface information BACnet 9 L Limitation of liability 3 O Other applicable documentation 3 Q Qualification 6 R Residual r...

Страница 39: ...Expansion module EM BAC MOD 01 39...

Страница 40: ...TROX GmbH 2017 TROX GmbH Heinrich Trox Platz 47504 Neukirchen Vluyn Germany 49 2845 202 0 49 2845 202 265 trox trox de http www troxtechnik com...

Отзывы: