DampPosMax_SC
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
not used
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the supply air
controller with the widest open damper blade
1, 4
Data point
BACnet: Analog Value Object – Instance 28 – value
and event state
Modbus: Register 53 (value) and register 54 (event
state)
DampPosMin_SC
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
not used
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the supply air
controller with the least wide open damper blade
1, 5
Data point
BACnet: Analog Value Object – Instance 29 – value
and event state
Modbus: Register 55 (value) and register 56 (event
state)
DampPosMax_TS
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the supply air
or room supply air controller with the widest open
damper blade
1, 4
For UNIVERSAL:
output of the damper blade posi-
tion of the supply air duct pressure controller in the
system with the widest open damper blade
1, 3, 4
Data point
BACnet: Analog Value Object – Instance 30 – value
and event state
Modbus: Register 57 (value) and register 58 (event
state)
Interface information
Data points – detailed description > Output variables
Expansion module EM-BAC-MOD-01
36