4.3.2 Output variables
ReadDeviceIdentification (only Modbus)
BMS access: RD
Equipment function: FH, RR, RR with RMF, EC, SC,
TAM, TAM with RMF
Function
Provides status information for the Modbus device
Data point
BACnet : see Device Object description
Modbus: Device response
–
Byte 0: Slave Address 1-99
–
Byte 1: Function Code 0x2B
–
Byte 3: Read Device ID Code 0x01
–
Byte 4: Conformity Level 0x01
–
Byte 5: More Follows 0x00
–
Byte 6: Next Object ID 0x00
–
Byte 7: Number of Objects 0x03
–
Byte 8: ID: VendorName 0x00
–
Byte 9: Obj-Length 9
–
Byte 10-18: Obj-Value "TROX GmbH"
–
Byte 19 ID: ProductCode 0x01
–
Byte 20: Obj-Length 23
–
Byte 21-43: Obj-Value "EM-BAC-MOD -
EASYLAB"
–
Byte 44 ID: MajMinRevision 0x02
–
Byte 45: Obj-Length 4
–
Byte 46-49: Obj-Value "V3.0"
ModeAct
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC
TROX UNIVERSAL
–
RE/RS with RMF, PR*/PD* with RMF
Function
Output of the operating mode of the volume flow
controller
For more information on each operating mode see
the description of the 'Mode' input variable
4.3.1 ‘Input variables’ on page 21 .
Functional values (BACnet / Modbus)
1/0 = No default
2/1 = Standard mode
3/2 = Reduced operation
4/3 = Increased operation
5/4 = Shut-off
6/5 = OPEN position
Data point
BACnet: Multistate Value Object – Instance 3
Modbus: Register 2
Interface information
Data points – detailed description > Output variables
Expansion module EM-BAC-MOD-01
26