PressSet_R
BMS access: WR RD
Equipment function:
EASYLAB
–
not used
TROX UNIVERSAL
–
PR*/PD*, PR*/PD* with RMF
Unit: Pa
Function
Local default setting of room pressure or duct pres-
sure setpoint value
Data point
BACnet: Analog Value Object – Instance 33
Modbus: Register 64
Volt_AO2
BMS access: WR RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
not used
Unit: V DC
Function
Enabling/disabling manual control
Upon enabling manual control the corresponding
symbol appears on the control panel.
Default setting of voltage for analogue output AO2
0 – 10 V DC, in increments of 0.1 V
Data point
BACnet: Analog Value Object – Instance 36
Modbus: Register 67
ManOp_Disable
BMS access: WR RD
Equipment function:
EASYLAB
–
FH, RR with RMF, TAM with RMF
TROX UNIVERSAL
–
RE/RS with RMF, PR*/PD* with RMF
Function
Enabling/disabling manual control
Upon enabling manual control the corresponding
symbol appears on the control panel.
For further information on manual control please
refer to the EASYLAB design manual.
FH: Operating mode default setting for a fume cup-
board controller, only with individual operating mode
default setting (stand-alone operation)
RMF: operating mode default setting for the entire
room
Functional values
0: Manual control has been enabled on the control
panel.
Operating mode defaults set on DI override BACnet
or Modbus defaults.
1: Manual control has been disabled on the control
panel.
Operating mode default settings from BACnet or
Modbus have the highest priority.
Data point
BACnet: Binary Value Object – Instance 4
Modbus: Bit list - bit 0 or register 1
Interface information
Data points – detailed description > Input variables
Expansion module EM-BAC-MOD-01
24