6. Diagnostics
6.1 Over Range Indication on
a Pellistor Gas Sensing
eModule
Incorrect readings will be given by a pellistor
gas sensing eModule if it is exposed to
gas concentrations that exceed its normal
working range.
When over range is detected on a pellistor
gas sensing eModule the Sentro 8
Sensorstation will switch into
Overrange
Lock
.
The screen will display the message
Pell Over
.
The transmitted output data will be clamped
at full scale.
The pellistor in the gas sensing eModule will
be switched into a protect state to prevent
oxidisation damage.
To Reset
Check that the gas has cleared.
Remove the eModule, wait five seconds and
refit the eModule.