ELECTRICAL REQUIREMENTS

3

check list

SECTION

W-006-A

WARNING!

THIS APPLIANCE MUST BE EARTHED

Meter

Incoming

supply

fuse

Meter

tails

Consumer

unit

Pull cord

isolating switch

Shower

unit

Fuse or

MCB

RCD

(can be part of

consumer unit)

80A or 100A

main switch

Table A

MCB

30/32A

32A
40A
40A
40A

40/45A

45A

cartridge

fuse

30A
35A
35A
45A
45A
45A
45A

unit 

rating

7.0kW
7.5kW
8.0kW
8.5kW
9.0kW
9.5kW

10.5kW

CIRCUIT PROTECTION

Fig.4

 Schematic of installation circuit

ELECTRICAL REQUIREMENTS

The installation, supply cable and circuit 

protection must conform with BS 7671 (IEE 

wiring regulations) and be sufficient for the 

amperage required.

The following notes are for guidance only:

1

 

The shower must only be connected to a 

230-240V ac supply. If you are installing a 

shower with a kilowatt rating above 9kW, it 

is advisable to contact the local electricity 

supply company.

1.1

  The electrical rating of the shower is shown 

on the rating label 

(Fig.3)

 within the unit.

2

 

 Before making any sort of electrical 

connection within the installation make 

sure that no terminal is live. If in any doubt, 

switch off the whole installation at the mains 

supply and remove the correct fuse.

3

 

The shower must be connected to its own 

independent electrical circuit. 

IT MUST NOT

 

be connected to a ring main, spur, socket 

outlet, lighting circuit or cooker circuit.

3.1

  The electrical supply must be adequate for 

the loading of the unit and existing circuits.

4

 

Check your consumer unit (main fuse box) 

has a main switch rating of 80A or above 

and that it has a spare fuse way which will 

take the fuse or Miniature Circuit Breaker 

(MCB) necessary for the shower 

(Fig.4)

.

4.1

  If your consumer unit has a rating below 

80A or if there is no spare fuse way, then the 

installation will not be straightforward and 

may require a new consumer unit serving 

the house or just the shower.

4.2

  You will need to contact the local electricity 

company. They will check the supply and 

carry out what is necessary. 

  For close circuit protection 

DO NOT

 use a 

rewireable fuse. Instead use a suitably rated 

Miniature Circuit Breaker (MCB) or cartridge 

fuse 

(see Table A)

.

5.1

  A 30mA residual current device (RCD) 

MUST

 be installed in all UK electric and 

pumped shower circuits. This may be part of 
the consumer unit or a separate unit.

Triton Showers,

Triton Road, Nuneaton,

Warwickshire, CV11 4NR

xxxx

Fig.3

Содержание Aspirante 8.5kW

Страница 1: ...on and keep it for future reference The shower installation MUST be carried out by a suitably qualified person in the sequence of this instruction book Installation and operating instructions Installe...

Страница 2: ...t is intended to operate the shower at pressures above the maximum or below the minimum stated b If the unit shows a distinct change in performance c If the shower is frozen 1 7 If it is intended to o...

Страница 3: ...pipes or fittings within 300mm of the shower unit as heat can transfer along the pipework and damage components 2 4 DO NOT fit any form of outlet flow control as the outlet acts as a vent for the hea...

Страница 4: ...ar to or below the minimum level The drop in pressure may be due to water being drawn off at other points in the house whilst the shower is in use If pressure drops appreciably below the minimum the h...

Страница 5: ...7 Plumbing installation 8 Electrical installation 9 Fit to the wall connect shower supplies 9 11 Fitting the cover 12 COMMISSIONING PROCEDURE 13 14 Connecting the PCB cable 14 USER OPERATING INSTRUCTI...

Страница 6: ...00 kPa 10 bar Maximum inlet temperature 28 C Minimum inlet temperature 2 C Inlet connection 15mm diameter Outlet connection BSP male thread MATERIALS ABS Backplate cover controls showerhead Acetal Spr...

Страница 7: ...m 94mm 300mm ENTRY POINTS DIMENSIONS WATER Left Top Bottom Side Back Right Bottom Side Back CABLE Left Top Bottom Side back Right None Back Back Others Others PLEASE NOTE Deviation from the approved e...

Страница 8: ...in any doubt switch off the whole installation at the mains supply and remove the correct fuse 3 The shower must be connected to its own independent electrical circuit IT MUST NOT be connected to a r...

Страница 9: ...while standing in a bath or shower cubicle It should be readily accessible to switch off after using the shower 7 Where shower cubicles are located in any rooms other than bathrooms all socket outlet...

Страница 10: ...ing to achieve your preferred shower temperature Fig 5 shows a typical system layout Refer to fig 6 for the correct siting of the shower Position the unit where it will NOT be in direct contact with w...

Страница 11: ...er hose or a blocked showerhead This may cause the PRD to operate When commissioning the showerhead must be removed from the flexible hose Failure to follow this procedure may cause the PRD to operate...

Страница 12: ...e wall This area MUST be left clear when plastering and tiling around the pipework in order to make the nut accessible for future adjustments NOTE An additional stopvalve complying with Water Regulati...

Страница 13: ...been chosen the trim can be fitted complete Should either top cable or top pipe entry have been chosen individually the trim has been designed to be separated and the appropriate trim section can be...

Страница 14: ...he wall and tighten the retaining screws which hold it to the wall Turn on the mains water supply and check for leaks in the pipework connection to the shower NOTE At this stage no water can flow thro...

Страница 15: ...earth conductor must be sleeved The outer sheath of the supply cable must be stripped back to the minimum The use of connections within the unit or other points in the shower circuit to supply power...

Страница 16: ...tes correctly minor adjustment may be necessary to align the control and spindle Should any difficulty arise recheck the points above While applying slight pressure to the front cover secure in positi...

Страница 17: ...could make the PRD operate Turn on the water supply to the shower at the isolating stop valve Switch on the electricity supply to the shower at the isolating switch Wait until water starts to flow fr...

Страница 18: ...fitted into the socket in one way The ribbon cable has a coloured edge which is lowermost when correctly fitted to the socket Guide the cover into position so that the knob spindle locates correctly...

Страница 19: ...ll start on the High setting To stop the shower The shower can be stopped by pressing the start stop button When pressed the phased shutdown will begin and water will cease to flow after a few seconds...

Страница 20: ...ges in ambient water temperature NOTE The preferred knob position on ECONOMY will give a different temperature to the same position on HIGH To decrease the shower temperature Turn the temperature cont...

Страница 21: ...ater pressure the unit automatically restores the power to the elements and returns to the original setting selected Phased shutdown In use every time the Start Stop button is pressed power is switche...

Страница 22: ...plate Unscrew the filter cap from the bottom of the inlet pipe Inspect the O ring for damage when the filter cap is removed When cleaning the filter DO NOT use a sharp object as it will cause damage I...

Страница 23: ...2 2 1 Check if stop valves are fully open Check if a blockage in the inlet filter 2 3 Increase in ambient water temperature 2 3 1 Readjust flow rate to give increased flow 2 3 2 Select economy power...

Страница 24: ...5 1 Thermal safety cut out device has operated Have the unit checked by a suitably qualified engineer or contact Customer Service 4 Pressure relief device has operated water ejected from PRD tube 4 1...

Страница 25: ...et S27411001 8 Water Outlet bottom TCO S27411002 9 Main Trimplate White 7054130 Black 7054144 10 Power PCB 7073732 11 Cover assembly including cover PCB Gloss Black S27410606 Gloss White S27410607 Gun...

Страница 26: ...der the following schemes Repic Producers take back scheme PTS registration number WEE EJ3466QV Valpak Distributor take back scheme DTS registration number 9659 All our electric products are labelled...

Страница 27: ...OF THE ELEMENTS USED HEATER ELEMENTS USED 2 OF THE ELEMENTS USED 0 1 2 H O T HOT COLD To START the shower button A B C or D can be pressed and water will flow from the shower Press A Start Stop and Hi...

Страница 28: ...including post code the model number and power rating of the product together with the date of purchase and where applicable details of the particular fault 2 If required the Customer Service Advisor...

Отзывы: