Voltage Selection Mode
Please follow below procedure to select the
output voltage by front panel.
1. Press the ON/TEST and OFF buttons
simultaneously to enter “Voltage Selection”
mode. The three LEDs labeled VOLTAGE
SELECTION MODE will flash when you have
entered this mode.
2. Press the ON/TEST button to select the
output voltage from 200 to 240.
3. After selecting the desired output voltage,
press the ON/TEST and OFF buttons
simultaneously to save your selection and
exit “Voltage Selection” mode.
2. Installation
2.2 Mounting (Tower)
The UPS system can be mounted in an upright
tower position when used with Tripp Lite’s
optional base stand kit (model 2-9USTAND, sold
separately). When mounting the UPS system in a
tower position, make sure the control panel is
closer to the top of the cabinet than the bottom.
The control panel can be rotated to match the
orientation of the UPS system. Pull the panel
out, rotate it and push it back into place as
shown.
Warning: The UPS system is very
heavy—be careful when moving or
lifting it.
2.3 Connection and Start-Up
1
Plug the UPS system into an electrical
outlet.
Note:
The UPS system does not include an input
power cord.
Connect a user-supplied power cord to the
IEC-320-C20 input receptacle. The power
cord should have an IEC-320-C19 connector
on one end and a plug appropriate for your
local site’s utility outlet on the other end.
The UPS system must be connected to a
dedicated circuit of sufficient amperage.
Refer to the UPS system nameplate for input
requirements.
After the UPS system is plugged in, the
following sequence of events will occur:
1. The fan will turn on and all LEDs will
illuminate momentarily.
2. The percent level LEDs (25%, 50%, 75%
and 100%) will illuminate one at a time.
3. The “LINE” and “LOAD” LEDs will
illuminate to indicate normal operation.
Note:
Power will not be supplied to the outlets until
the UPS system is turned on.