Troubleshooting manual
AT.654254.050 ver.1.0
2.
Go to
→
«Commissioning»
→
«U/F»
→
«U/F curve».
•
set-up voltage and fre-
quency points 4 as the max-
imum motor operation volt-
age and frequency. Voltage
here is the VSD output. Volt-
age can be set equal to sup-
ply voltage;
•
then
press
parameter
«Straight U/F», the control-
ler automatically trans-
forms the curve in line.
3.
Go to «Commissioning» –
«
Modes of start
» and make sure that there is
inst
alled startup mode «Soft».
Now the VSD is ready for no-load test.
TO START A MOTOR PRESS
TO STOP A MOTOR PRESS