TMCM-1311 TMCL Firmware V1.11 Manual (Rev. 1.17 / 2015-NOV-05)
76
www.trinamic.com
Number Axis Parameter Description
Range [Unit]
Acc.
195
Referencing
switch speed
Similar to parameter no. 194, the speed for the
switching point calibration can be selected.
327.678.000…
+327.679.999
[pps]
RWE
196
End switch
distance
This parameter provides the distance between
the end switches after executing the RFS
command (mode 2 or 3).
0… +2.147.483.647
[µsteps]
[encoder steps]
R
198
Clear on null
This parameter can be used to set bit 2 of axis
parameter 201.
0
Delete bit 2 of axis parameter 201.
1
Clear encoder on next null channel
event (set bit 2 of axis parameter 201).
0/1
RW
200
Boost current
Current used for acceleration and deceleration
phases.
If set to 0 the same current as set by axis
parameter 6 will be used.
0… 255
𝐼𝐼
𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝
=<
𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣
>×
4.2
𝐴𝐴
255
𝐼𝐼
𝑅𝑅𝑅𝑅𝑅𝑅
=<
𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣
>×
3
𝐴𝐴
255
RWE
201
Encoder mode
Operation mode of the encoder.
4 (bit 2)
Clear encoder on next null channel
event.
8 (bit 3)
Clear encoder on every null channel
event.
16 (bit 4) Null channel polarity (active high
when set)
4, 8, 16
RWE
202
Motor Resolution Motor fullstep resolution.
0… 400
Default: 200
[fullsteps]
RW
204
Freewheeling
Time after which the power to the motor will
be cut when its velocity has reached zero.
Parameter is not valid in closed loop mode!
0… 65535
0 = never
[msec]
RWE
206
Actual load value Readout of the actual load value used for stall
detection (stallGuard2).
0… 1023
R
207
Max encoder
deviation error
flag
When maximum deviation is reached, motor is
stopped/switched off. This flag shows this
condition.
0/1
R
208
Driver error flags
Bit 0
stallGuard2 status
(1:
threshold reached)
Bit 1
Overtemperature
(1: driver is shut down due to
overtemperature)
Bit 2
Pre-warning overtemperature
(1: t
reshold is exceeded)
Bit 3
Short to ground A
(1: short condition dete
ted, driver
currently shut down)
Bit 4
Short to ground B
(1: short condition detected, driver
currently shut down)
Bit 5
Open load A
(1: no chopper event has happened
during the last period with constant
coil polarity)
Bit 6
Open load B
(1: no chopper event has happened
during the last period with constant
coil polarity)
Bit 7
Stand still
(1: no step impulse occurred on the
step input during the last 2^20 clock
cycles)
0/1
R