37
Calibrate light sensor
Tap the "Calibrate light sensor" setting option to calibrate the light sen-
sor.
Calibration of the light sensor
Illuminance can be managed in the light sensor calibration area. For
proper calibration, the luxmeter must be placed in the centre of the
work area and the room should be darkened so that there is no daylight.
Then the illuminance must be adjusted (see instructions on the
screen). The illuminance (in percent) can be adjusted manually with the
slider on the right-hand side. The recommended illuminance is also
displayed on the screen; this is 500lx by default. Tap the tick to apply
the changed settings.
Note:
During calibration, the luxmeter should be placed at the darkest or a
defined measuring point of the work area for effective measurement.
COMMISSIONING
Change password
Tap the "Change password" setting option to change the device pass-
word.
New password
To be able to change the device password, the old password must first
be entered. The new password must then be entered twice. Tap the tick
to confirm the entry.
Note:
Secure passwords should be at least 10 characters long, consist of up-
per and lower case letters and special characters.
Содержание LiveLink LightGrid
Страница 1: ...LIVELINK LIGHTGRID...