PAGE 26
QUANTUM NXT DI HEATER OPERATION / MAINTENANCE MANUAL
All of the Boolean data type registers are false when they contain the
value 0 and true when they contain a 1. When writing to Boolean
registers, false is represented by the value 0 and true is represented by
the value 1.
The ‘short’ data type registers are in 10ths of units. For example, when
the set point is intended to be 25.0°C, the value would read 250.
Port settings defaults are as follows:
Station: 1
Baud Rate: 115200
Data Bits: 8
Parity: Even
Stop Bits: 1
For more information regarding Modbus communication please visit
www.modbus.org
.
Name
HMI/PLC
ADDRESS
MODBUS
ADDRESS
ADDRESS
x06
Type
Data
Bytes
Perm
Set Point
$M100/D590
W42101
402100
Reg Short
2
R/W
Remote On/Off
$M101/D611
W42102
402101 Reg Bool
2
R/W
Process Temperature
$M102/D602
W42103
402102 Reg Short
2
R
Duty Cycle
$M103/D8001
W42104
402103 Reg Short
2
R
Mode
$M104/D610
W42105
402104 Reg Bool
2
R
Alarm Status
$M105/D11
W42106
402105 Reg Bool
2
R
Alarm Pressure
$M106/D12
W42107
402106 Reg Bool
2
R
Alarm Liquid Leak
$M107/D13
W42108
402107 Reg Bool
2
R
Alarm Liquid Level
$M108/D14
W42109
402108 Reg Bool
2
R
Alarm Flow
$M109/D15
W42110
402109 Reg Bool
2
R
Alarm Over Temp.
$M110/D16
W42111
402110 Reg Bool
2
R
Table 3-1: Modbus Mapping