QUANTUM NXT DI HEATER OPERATION / MAINTENANCE MANUAL
PAGE 11
2.4.f Low/Stop Flow
Low/Stop Flow is a function that can be turned on by checking the
Low/Stop Flow box on the configuration page. This function, when turned
on, will prevent power to the heater elements if the flow meter senses
flow under the set value of the flow switch. See Section 3.5.e for more
details.
2.4.g Continuous High
When the heater is operated continuously above the recommended 85%
for longer than 30 minutes, the heater will show a warning on the home
screen as well as show a continuous alarm on the alarm page. This alerts
the user that either the system is overworked, or element failures have
caused the heater output to increase above the recommended limit.
Pressing the reset button will silence the audible beep, but the alarm will
repeat if the heater continues to output above 85%.