Table 22. Evaporator Fan Performance 12½ Tons TC*150D Downflow or Horizontal
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
3-HP Standard Motor & Field Supplied Low Static Drive
(i)
(i)
Field Supplied Fan Sheave BK90 required. Field Supplied Belt may be necessary.
3-HP Standard Motor & Sheaves
4000
—
—
—
—
—
—
565
0.93
599
1.03
632
1.15
663
1.27
695
1.38
727
1.48
757
1.59
4500
—
—
—
—
571
1.10
603
1.21
634
1.31
665
1.43
694
1.56
723
1.69
750
1.82
778
1.94
5000
547 1.18
581
1.30
613
1.42
643
1.54
672
1.67
700
1.78
727
1.91
755
2.05
781
2.19
806
2.34
5500
595 1.55
627
1.68
656
1.81
685
1.94
711
2.08
737
2.21
763
2.34
788
2.47
813
2.62
837
2.77
6000
643 1.99
673
2.12
701
2.26
727
2.41
752
2.56
777
2.71
801
2.85
825
2.99
848
3.13
871
3.27
Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
CFM
RPM BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
3 HP Standard Motor & Sheaves
3 HP Standard Motor & High Static Drive Accessory
4000
786 1.70
813
1.81
841
1.91
867
2.02
893
2.12
919
2.22
943
2.32
966
2.41
989
2.50 1011 2.60
4500
806 2.06
834
2.19
861
2.31
886
2.43
911
2.56
935
2.67
960
2.79
983
2.90 1005 3.02 1028 3.13
5000
830 2.48
856
2.62
882
2.76
907
2.89
931
3.02
955
3.16
977
3.30 1001 3.44 1022 3.56 1045 3.70
5500
861 2.93
884
3.10
906
3.25
930
3.41
953
3.56
976
3.70
999
3.86 1021 4.00 1043 4.15 1064 4.31
6000
894 3.43
916
3.61
938
3.79
959
3.97
980
4.15 1000 4.31 1019 4.46 1040 4.62 1061 4.78 1082 4.95
5-HP Oversized Motor & Sheaves
5-HP Oversized Motor & Field Supplied Drive
(ii)
(ii)
5-HP Oversized Motor with Field Supplied Motor Sheave IVL40 required. Field Supplied Belt may be necessary.
*For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to "Motor & Sheave/Fan Speed" tables to determine operating range.
For Standard Evaporator Fan Speed (RPM), reference
Table 50
.
For Oversized Evaporator Fan Speed (RPM), reference
Table 53
.
Fan motor heat (MBH) = 3.15 x Fan BHP.
Notes:
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data. Refer to
Table 54
to
determine additional static pressure drop due to other options/accessories.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature
motor failure. Our product's warranty will not be affected.
Performance Data