66
RT-PRC024-EN
Performance Data
(25 Tons High Efficiency)
Table 48. Evaporator Fan Performance 25 Tons TC*301C Standard Refrigeration or TXV System Downflow or Horizontal
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
7.5-HP Standard Motor & Field Supplied Extra Low Static Drive
7.5-HP Standard Motor & Low Static Drive Accessory
5000*
—
—
—
—
—
—
—
—
—
—
576
1.56
606
1.71
635
1.88
663
2.05
690
2.22
6500*
—
—
—
—
576
2.11
601
2.27
625
2.43
649
2.59
674
2.78
698
2.97
722
3.18
746
3.38
7000*
—
—
579
2.32
608
2.54
633
2.73
656
2.89
678
3.06
700
3.25
723
3.44
745
3.65
768
3.87
7500* 582
2.59
611
2.78
640
3.02
665
3.24
687
3.43
708
3.61
729
3.79
749
3.98
770
4.19
792
4.41
8000
616
3.07
645
3.31
672
3.56
696
3.80
719
4.02
739
4.22
759
4.41
778
4.60
797
4.81
817
5.03
8500
650
3.66
678
3.90
704
4.16
728
4.43
750
4.68
771
4.90
790
5.10
808
5.31
826
5.52
844
5.74
9000
685
4.31
712
4.56
737
4.83
760
5.12
782
5.39
802
5.65
821
5.88
839
6.09
856
6.30
873
6.53
9500
721
5.04
746
5.30
770
5.58
792
5.88
814
6.18
834
6.46
853
6.72
870
6.96
887
7.18
903
7.41
10000 756
5.85
780
6.12
803
6.41
825
6.72
846
7.04
866
7.35
884
7.64
902
7.90
918
8.14
934
8.38
10500 791
6.74
814
7.03
836
7.33
858
7.64
878
7.98
898
8.31
916
8.62
—
—
—
—
—
—
11000 827
7.71
849
8.02
870
8.33
891
8.63
—
—
—
—
—
—
—
—
—
—
—
—
7.5-HP Standard Motor & Drive
7.5-HP Standard Motor & High Static Drive Accessory
Continued
For Standard Evaporator Fan Speed (RPM), reference
Table 50
.
For Standard Motor & Low Static Drive Accessory Fan Speed
(RPM), reference
Table 51
.
For Oversized Evaporator Fan Speed (RPM), reference
Table 53
.
Fan motor heat (MBH) = 3.15 x Fan BHP.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to
Table 54
to determine additional static pressure
drop due to other options/accessories.
Factory supplied motors, in commercial equipment, are definite
purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the
full horsepower range of our fan motors as shown in our tabular
data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
*
For 5000, 6500, 7000 and 7500 CFM, unit applications below 320
CFM/Ton are only applicable to TCD models only (No Gas
Heat). See below for restrictions.
•
Electric heaters restricted on applications below 320 CFM/Ton.
•
Dehumidification (Hot Gas Reheat) or TXV with Frostat and
Crankcase Heaters are required on applications below 320
CFM/Ton.
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
7.5-HP Standard Motor & Drive
5000* 716
2.41
741
2.60
765
2.80
789
3.00
812
3.20
6500* 769
3.59
792
3.80
814
4.01
836
4.22
857
4.44
7000* 790
4.09
812
4.31
833
4.53
854
4.76
875
4.99
7500* 813
4.65
833
4.88
854
5.12
874
5.36
894
5.59
8000
837
5.26
857
5.51
876
5.76
896
6.01
915
6.26
8500
863
5.97
881
6.21
900
6.46
919
6.73
937
6.99
9000
890
6.76
908
7.00
925
7.25
943
7.52
961
7.79
9500
919
7.64
936
7.88
952
8.13
969
8.40
985
8.67
10000 949
8.62
—
—
—
—
—
—
—
—
10500
—
—
—
—
—
—
—
—
—
—
11000
—
—
—
—
—
—
—
—
—
—
7.5-HP Standard Motor & High Static Drive Accessory
Содержание Voyager TC Series
Страница 10: ...10 RT PRC024 EN Features and Benefits Figure 1 Voyager Factory Installed Options Factory Installed Options...
Страница 84: ...84 RT PRC024 EN Figure 3 12 5 25 Tons Cooling with Optional Electric Heat Typical Wiring...
Страница 106: ......