9
UNT-SVX10G-E4
Installation
Table 3 - General data - FED without air connections
230V/50Hz/1pH, Reversible coil, 2 Pipes
Speed at ESP = 0Pa
Unit size
100
200
300
400
500
600
Airflow (1)
(m3/h)
310
441
609
1014
1591
1591
Standard coil, cooling mode
Air inlet conditions : 27°C/47%, Water : 7/12°C, Constant delta T°
Total / sensible cooling capacity (1)
(kW)
1.4 / 1.1
1.9 / 1.6
3.3 / 2.5
5.2 / 4.1
6.1 / 4.9
9.7 / 7.3
FCEER / Eurovent Energy class (2)
186 / B
185 / B
174 / B
133 / A
87 / A
125 / A
Water flow (1)
(l/s)
0.068
0.093
0.16
0.25
0.29
0.46
Water pressure drop (1)
(kPa)
18.3
8.2
15.5
39
60.8
48.2
Water content
(l)
0.5
0.6
1.3
1.5
1.5
2.8
Water connection
1/2" ISO R7 female gas
Standard coil, heating mode
Air inlet : 20°C, Water inlet : 50°C, Water flow from cooling mode
Heating capacity (1)
(kW)
1.9
2.7
4.3
6.9
8
11.4
FCCOP / Eurovent Energy class (2)
240 / B
250 / B
138 / A
173 / A
103 / A
42 / A
Water flow (1)
(l/s)
0.068
0.093
0.16
0.25
0.29
0.46
Water pressure drop (1)
(kPa)
15.1
6.9
13.6
38
60
48
Electric heater (option)
Electric heater
(W)
-
500
500 / 750
1000 / 3000
1000 / 3000
1000 / 3000
Power supply
(V-Ph-Hz)
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
Power absorbed (speeds 1/3/5)
(W)
3.3/5.8/12
3.7/8.7/19
4.8/18/43
8/39/65
36/112/159
36/112/159
Absorbed current (min/max)
(A)
-
2.2
2.2/3.3
4.3/13
4.3/13
4.3/13
Fan motor
Maximun external static pressure
(Pa)
50
60
90
90
90
90
Sound levels
Sound Power Level (speeds 1/3/5) (3)
(dB(A))
32/41/49
35/45/53
37/52/61
42/57/62
56/66/69
56/66/69
Sound Pressure Level (speeds 1/3/5) (4)
(dB(A))
23/32/40
26/36/44
28/43/52
33/49/53
46/56/60
46/56/60
NR Level (speeds 1/3/5) (4)
21/28/36
22/31/40
24/38/49
29/44/49
42/54/56
42/54/56
NC Level (speeds 1/3/5) (4)
19/27/34
20/30/38
22/37/47
27/42/47
40/52/50
40/52/50
Voltage range
Minimum voltage
(V)
2
2.3
2.6
3
3
3
Maximum voltage
(V)
5.1
5.8
7.6
9
9
7
Speed 1/3/5 -> speed low/medium/high
(1) At high speed in compliance with Eurovent conditions
(2) EER Eurovent ratio and class definition (speed low/medium/high)
(3) Levels according to Eurovent specification 8/2 (ISO 3741/88) and Eurovent FC Certification For 400/500/600 as per voltages declared to Eurovent.
(4) Values calculated from sound levels with hypothetical acoustic attenuation of 9dB
UNT-SVX10G-BAT1_Mise en page 1 7/26/2013 2:41 PM Page 9