background image

Installation

11

UNT-SVX10G-E4

Operating limits at air side
(temperature and airflow)

Cooling mode

The unit must not be installed in an
environment where the temperature
exceeds 40°C.

Heating mode

The discharge air temperature must
not exceed 70°C to avoid damaging
the internal unit insulation.

The manufacturer recommends to
not exceed 55°C discharge air
temperature to ensure ideal comfort
and avoid air stratification.

Operating limits at water
side

Water pressure must not exceed 
15 bar.

Water temperature must not 
exceed 95°C.

Minimal water temperature
depends on glycol percentage.

Water quality
recommendations

At installation and then yearly, the
manufacturer recommends having
water analyzed for bacteria (ferro-
bacteria, bacteria generating H2S
and reducing sulfates) and also a
chemical analysis, to avoid
corrosion and scaling. The water
circuit must include water treatment
devices: filters,
additives,intermediate exchangers,
purges,vents, isolating valves,
etc.depending on the results of
these analyses. 

CAUTION!  Proper Water
Treatment!

The use of untreated or improperly
treated water in this equipment may
result in scaling, erosion, corrosion,
algae or slime. It is recommended
that the services of a qualified water
treatment specialist be engaged to
determine what water treatment, if
any, is required. Trane assumes no
responsibility for equipment failures
which result from untreated or
improperly treated water, or saline
or brackish water

CAUTION!  Coil
recommendation

Coil must not be used in a corrosive
environment, to prevent corrosion
of aluminium components.  Coated
fin is available as an option.
Contact your local Trane sales office
for advice.

UNT-SVX10G-BAT1_Mise en page 1  7/26/2013  2:41 PM  Page 11

Содержание UniTrane FCD

Страница 1: ...Sizes 101 103 203 204 304 306 406 408 508 512 612 721 UniTrane FED ducted fan coil units Sizes 100 200 300 400 500 600 Installation Operation Maintenance July 2013 UNT SVX10G E4 UNT SVX10G BAT1_Mise...

Страница 2: ...ures for system leak testing on low and high pressure side are given in the chapter Installation Always provide a pressure regulator 2 Disconnect the main power supply before any servicing on the unit...

Страница 3: ...uipment Regular maintenance ensures that any malfunction is detected and corrected in good time and minimizes the possibility that serious damage will occur Finally regular maintenance ensures the max...

Страница 4: ...ensate drainage connection 23 Electrical connection 28 Connecting the thermostats 32 Main power supply 39 External static pressure and airflow curves 40 Water pressure drop curves 48 Pre start checkou...

Страница 5: ...ortant information such as the customer order number job name unit model size coil type presence of an electric heater motor type unit handing speed wiring and so on See Figure 1 Figure 1 Unit identif...

Страница 6: ...number max 25 alphanumeric characters Indicates job name max 25 alphanumeric characters Indicates personal customer tag max 22 alphanumeric characters 1 Zone control 2 Cascade control Water Right han...

Страница 7: ...ower supply V Ph Hz 230 1 50 230 1 50 230 1 50 230 1 50 230 1 50 230 1 50 230 1 50 230 1 50 230 1 50 230 1 50 230 1 50 230 1 50 Power absorbed speeds 1 3 5 W 11 16 27 18 25 40 19 26 41 23 37 54 26 42...

Страница 8: ...er supply V Ph Hz 230 1 50 230 1 50 230 1 50 230 1 50 230 1 50 230 1 50 230 1 50 230 1 50 230 1 50 Power absorbed speeds 1 3 5 W 23 37 54 26 42 61 36 58 82 36 59 82 53 87 118 53 87 124 118 13 9 164 11...

Страница 9: ...000 3000 1000 3000 Power supply V Ph Hz 230 1 50 230 1 50 230 1 50 230 1 50 230 1 50 230 1 50 Power absorbed speeds 1 3 5 W 3 3 5 8 12 3 7 8 7 19 4 8 18 43 8 39 65 36 112 159 36 112 159 Absorbed curre...

Страница 10: ...Ph Hz 230 1 50 230 1 50 230 1 50 230 1 50 230 1 50 Power absorbed speeds 1 3 5 W 3 7 8 7 19 4 8 18 43 6 25 46 23 69 100 25 76 109 Absorbed current min max A 2 2 2 2 3 3 4 3 13 4 3 13 4 3 13 Fan motor...

Страница 11: ...educing sulfates and also a chemical analysis to avoid corrosion and scaling The water circuit must include water treatment devices filters additives intermediate exchangers purges vents isolating val...

Страница 12: ...h air controllers are available as a factory mounted option D 100 mm duct connection D 125 mm duct connection Fixed airflow controller 30 m3 h for D 100 mm duct Fixed airflow controller 45 m3 h for D...

Страница 13: ...r 125 mm only by placing the two plastic restrictors as indicated in Figure 5 Figure 3 Fresh air adapter 1 Fresh air controller Figure 4 Fresh air controller membrane 1 Fresh air controller 2 Membrane...

Страница 14: ...efer to the notice supplied with the accessory 1 2 3 Mounting the unit in the ceiling Two methods can be used to mount the unit in the ceiling A minimum of 3 fixation points are necessary up to the un...

Страница 15: ...300 3 4 858 579 922 2 338 15 1 6 FCD 406 408 FED 400 3 4 1008 579 1063 2 338 15 1 6 FCD 304 306 High capacity FED 300 High capacity 4 858 637 1068 5 15 1 6 FCD 406 408 High capacity FED 400 High capac...

Страница 16: ...he unit is not mounted with a slight slope the condensates will not drain correctly through the hole provided Refer to Figures 9 and 10 In order to be sure that the unit is correctly installed it is h...

Страница 17: ...s of the unit the ductwork must be as short as possible with a minimum number of bends Table 6 Inlet and outlet connections FCD 101 103 203 204 304 306 406 408 508 512 612 721 Circular connection 160...

Страница 18: ...onnection 200 mm 200 1 1 or 2 2 or 3 2 or 3 2 or 3 3 or 4 Oblong connection equivalent 250 mm 250mm 1 1 1 or 2 1 or 2 2 2 Rectangular connection for 39 mm deep 194 x 418 mm 194 x 568 mm 194 x 798 mm 1...

Страница 19: ...ctor Use a suitable counter spanner Tighten to torque 25 N m The water inlet is on the bottom of the coil and the water outlet is on the top of the coil On 4 pipe coils the heating connections are loc...

Страница 20: ...t Unit size 101 103 203 204 304 306 406 408 508 512 612 721 Standard 2 pipe coil Customer connection 1 2 Flat gasket 1 2 Flat gasket 1 2 Flat gasket 1 2 Flat gasket 1 2 Flat gasket 3 4 Flat gasket 3 4...

Страница 21: ...g cold water connection 1 2 Flat gasket 1 2 Flat gasket 1 2 Flat gasket 1 2 Flat gasket 1 2 Flat gasket 3 4 Flat gasket 3 4 Flat gasket Customer leaving hot water connection 1 2 Gas 1 2 Gas 1 2 Gas 1...

Страница 22: ...lve Units have undergone extensive tests for condensates NF EN 1397 para 5 3 however If a constant water flow is passing through the coil and the fan is not running for a long period of time condensat...

Страница 23: ...t It is recommended to secure connection between the tube and the drain with a clamp or a collar CAUTION Make sure there is no counter slope or debris which would prevent condensate drainage see Figur...

Страница 24: ...he condensate pump is equipped with a floating sensor which will stop chilled water flow as soon as the alarm level is reached while continuing to evacuate condensate water It is recommended to secure...

Страница 25: ...ntrol 1 Condensate tray 2 Condensate level sensor 3 Condensate tube suction 4 Condensate tube discharge 5 Vent It is recommended to secure connection between the tube and the drain with a clamp or a c...

Страница 26: ...densate drainage with condensate pump for on off GP control or ZN control A Position the vent upwards 1 Water 2 Air B No negative discharge WARNING X A 1 1 2 B 60 mm 10 mm m L 10 mm m H UNT SVX10G BAT...

Страница 27: ...10 mm m A Discharge height H Discharge length L Pump manufacturer 5m 10m 20m 30m Sauerman GP 1m 9 5 9 0 8 2 7 4 Sauerman GP 2m 7 0 6 5 5 7 4 9 Sauerman GP 3m 5 0 4 6 3 9 3 4 Sauerman GP 4m 4 0 3 6 3...

Страница 28: ...of the installer The factory mounted electric heaters are fitted with a safety device that prevents them from functioning if the fan breaks down beware of automatic resetting systems All faults must...

Страница 29: ...1000 Table 11 Minimum airflow m3 h in order to not damage heating elements FED Unit size 100 200 300 400 500 600 500W 80 80 80 750W 120 120 1000W 160 160 160 160 160 1500W 240 240 240 240 2000W 320 3...

Страница 30: ...tage Airflow range V min 3 V medium 6 9 V max 9 FED500 FED600 Voltage Airflow range V min 3 5 V medium 5 2 V max 7 Minimum Voltage 2 pipe electric heat heating mode FED100 Electric heater capacity 500...

Страница 31: ...ting system C Special selection operating system zone D Airflow pressure drop system curve E Standard selection operating system zone Figure 22 FED 300 with Electric Heater 1500 W 2000 W A 320 m3 hr m...

Страница 32: ...TION To avoid damaging equipment never connect several fan coils in parallel to one thermostat Each fan coil must be connected to its own thermostat Table 12 Available thermostat types FCD Figure 23 T...

Страница 33: ...ed 3 Purple speed 4 Grey speed 5 Black cable not available Brown speed 6 Each unit comes with a wiring diagram attached to the unit Wiring diagram numbers Unit without control wiring only terminal blo...

Страница 34: ...UNT SVX10G E4 34 Installation Figure 25 Interconnection wirings On Off controls thermostat L M for FCD UNT SVX10G BAT1_Mise en page 1 7 26 2013 2 41 PM Page 34...

Страница 35: ...35 UNT SVX10G E4 Figure 26 Interconnection wirings On Off controls thermostat N for FCD Installation UNT SVX10G BAT1_Mise en page 1 7 26 2013 2 41 PM Page 35...

Страница 36: ...r 4 pipe 2 tubi freddo riscaldamento elettrico 4 tubi 2 buizen koelen elektrische verwarming 4 buizen 2 tubos enfriador calefaccion el ctrica 4 tubos 2 tubes froid 2 kalte Rohre 2 pipe cooling 2 tubi...

Страница 37: ...37 UNT SVX10G E4 Installation Figure 28 Interconnection wirings On Off controls thermostat P for FCD UNT SVX10G BAT1_Mise en page 1 7 26 2013 2 41 PM Page 37...

Страница 38: ...UNT SVX10G E4 38 Installation Figure 29 Interconnection wirings On Off controls thermostat P E for FCD UNT SVX10G BAT1_Mise en page 1 7 26 2013 2 41 PM Page 38...

Страница 39: ...tion To connect main power supply refer to Figures 30 31 Figure 30 Units with On Off control PE L N BK 1A BU 2A 230V 50Hz 1Ph N T N L 1F50 1F50 X 7 Figure 31 Units with modulating communicating contro...

Страница 40: ...air duct connections s Figure 33 External Static Pressure FCD 103 with G3 filter D1 Discharge plenum only 200 mm air duct connection s D2 Discharge plenum return plenum 200 mm air duct connections s 0...

Страница 41: ...ons s Figure 35 External Static Pressure FCD 204 with G3 filter D1 Discharge plenum only 200 mm air duct connection s D2 Discharge plenum return plenum 200 mm air duct connections s 0 10 20 30 40 50 6...

Страница 42: ...gure 37 External Static Pressure FCD 306 with G3 filter D1 Discharge plenum only 200 mm air duct connection s D2 Discharge plenum return plenum 200 mm air duct connections s 0 10 20 30 40 50 60 70 80...

Страница 43: ...ure 39 External Static Pressure FCD 408 with G3 filter D1 Discharge plenum only 200 mm air duct connection s D2 Discharge plenum return plenum 200 mm air duct connections s 0 10 20 30 40 50 60 70 80 9...

Страница 44: ...1 External Static Pressure FCD 512 with G3 filter D1 Discharge plenum only 200 mm air duct connection s D2 Discharge plenum return plenum 200 mm air duct connections s 0 10 20 30 40 50 60 70 80 90 100...

Страница 45: ...air duct connections s Figure 43 External Static Pressure FCD 721 with G3 filter D1 Discharge plenum only 200 mm air duct connection s D2 Discharge plenum return plenum 0200mm air duct connections s 0...

Страница 46: ...nnection s D2 Discharge plenum return plenum 200 mm air duct connections s Figure 45 External Static Pressure FED 200 D1 Discharge plenum only 200 mm air duct connection s D2 Discharge plenum return p...

Страница 47: ...arge plenum return plenum 200 mm air duct connections s Figure 47 External Static Pressure FED 400 D1 Discharge plenum only 200 mm air duct connection s D2 Discharge plenum return plenum 200 mm air du...

Страница 48: ...t connections s Figure 49 External Static Pressure FED 600 D1 Discharge plenum only 200 mm air duct connection s D2 Discharge plenum return plenum 200 mm air duct connections s 0 10 20 30 40 50 60 70...

Страница 49: ...7 Size 721 4 FCD Size 406 408 FED 400 Figure 51 Water pressure drop through the coils Cooling mode High capacity 2 pipe coil 1 FCD Size 101 103 FED 100 5 FCD Size 406 408 FED 400 2 Size 203 6 Size 50...

Страница 50: ...4 FCD Size 406 408 FED 400 0 1 10 100 10 100 1000 5000 kPa l h 1 2 34 5 6 7 200 Figure 53 Water pressure drop through the coils Heating mode High capacity 2 pipe coil 1 10 100 10 100 1000 kPa l h 1 2...

Страница 51: ...5000 1 FCD Size 101 103 Standard capacity FED 100 2 FCD Size 203 204 Standard capacity FED 200 3 FCD Size 304 306 Standard capacity FED 300 4 FCD Size 406 408 Standard capacity FED 400 5 Size 508 512...

Страница 52: ...2 1 2 2 way on off control Kv valve 1 0 1 0 1 0 2 way ZN 523 control Kv valve 1 0 1 0 1 0 3 way on off control Kv valve 1 0 1 0 1 0 3 way ZN523 control Kv valve 1 0 1 0 1 0 Unit size 100 200 300 400 5...

Страница 53: ...Installation 53 UNT SVX10G E4 Figure 55 Pressure drop through the valves m3 h UNT SVX10G BAT1_Mise en page 1 7 26 2013 2 41 PM Page 53...

Страница 54: ...e water loop is balanced No foreign bodies in the unit Adjuster and balancer bends adjusted and insulated Units checked in operation switches thermostats undue noise or vibration etc Instructions give...

Страница 55: ...The electric heater element connections are on the coil side 3 The fan board may have to be removed See Servicing the fan motor assembly section 4 Do the operations in reverse order to reassemble 5 W...

Страница 56: ...2 Pull down the filter using a screwdriver To put the filter back hold the filter at the top of the frame with one hand Push to clip the filter back into place at the bottom with the other hand Figure...

Страница 57: ...e The coil is visible 3 Unscrew 4 screws on the collector side and 2 screws on the opposite side 3 on Figure 60 4 Remove the coil Note If the option Accessibility pack has been chosen remove one screw...

Страница 58: ...board and unscrew the solid state relay Push aside the bundle of wires 3 Remove the 2 screws on each side panel 4 Figure 62 4 Remove the fan board Note If the option Accessibility pack has been chosen...

Страница 59: ...m sampling of the units installed in the building between 3 and 5 to check 1 the state of cleanliness of the condensate trays 2 the condensates flow correctly use a water spray 3 the condensate pumps...

Страница 60: ...ature setting 4 Operating mode selector Heat Heating mode Cool Cooling mode 20 25 3 0 1 5 1 0 1 3 2 ON OFF FAN 3 2 1 Thermostat type E 1 ON OFF selector 2 Fan speed selection 3 Temperature setting l O...

Страница 61: ...Notes 61 UNT SVX10G E4 UNT SVX10G BAT1_Mise en page 1 7 26 2013 2 41 PM Page 61...

Страница 62: ...Notes UNT SVX10G E4 62 UNT SVX10G BAT1_Mise en page 1 7 26 2013 2 41 PM Page 62...

Страница 63: ...Notes 63 UNT SVX10G E4 UNT SVX10G BAT1_Mise en page 1 7 26 2013 2 41 PM Page 63...

Страница 64: ...hensive building services and parts For more information visit www Trane com Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifica...

Отзывы: