UNT-SVX10G-E4
8
Installation
Table 2 - General data - FCD with inlet/discharge air connections (Dia. 200mm) and EU3 filter
230V/50Hz/1pH, Reversible coil, 2 Pipes
Speed at ESP = 50Pa
Unit size
204 (*)
304 (*)
306
406
408
508
512
612
721
Airflow (1)
(m3/h)
145
152
402
400
544
585
864
869
1990
Standard coil, cooling mode
Air inlet conditions : 27°C/47%, Water : 7/12°C, Constant delta T°
Total/sensible cooling capacity (1)
(kW)
0.84/0.
68
1.2/0.8
5
2.6/2
2.9/2.1
3.7/2.7
3.3/2.4
4.3/3.3
6.3/4.5
11/8.4
EER/Eurovent Energy class (2)
24/E
28/D
42/C
47/C
41/C
35/D
32/D
45/C
40/D
Water flow (1)
(l/s)
0.04
0.056
0.13
0.14
0.18
0.16
0.2
0.3
0.53
Water pressure drop (1)
(kPa)
1.9
2.5
11.6
13.5
20.7
22.2
35.2
22.1
41
Water content
(l)
0.6
1.3
1.3
1.5
1.5
1.5
1.5
2.8
3.3
Water connection
1/2" ISO R7 female gas
3/4" ISO R7 female gas
Standard coil, heating mode
Air inlet : 20°C, Water inlet : 50°C, Water flow from cooling mode
Heating capacity (1)
(kW)
1.2
1.4
3.3
3.5
4.5
4.2
5.7
6.9
14
COP/Eurovent Energy class (2)
32/D
32/D
53/C
56/C
50/C
45/C
42/C
49/C
50/C
Water flow (1)
(l/s)
0.04
0.056
0.13
0.14
0.18
0.16
0.2
0.3
0.53
Water pressure drop (1)
(kPa)
1.5
2.5
10.1
10.9
16.7
18.7
29.7
19.1
38
Electric heater (option)
Electric heater
(W)
500/
1000
500/
1500
500/
1500
500/
1500
1500/
4000
1500/
3000
1500/
4000
1500/
4000
1500/
4000
Power supply
(V-Ph-Hz)
230-1-
50
230-1-
50
230-1-
50
230-1-
50
230-1-
50
230-1-
50
230-1-
50
230-1-
50
230-1-50
Power absorbed (speeds 1/3/5)
(W)
23/37
/54
26/42
/61
36/58
/82
36/59
/82
53/87
/118
53/87
/124
118/13
9/164
119/14
5/171
146/254/283
Absorbed current (min/max)
(A)
2.2/4.3
2.2/6.5
2.2/6.5
2.2/6.5
6.5/17.4
6.5/13
6.5/17.4
6.5/17.4
6.5/17.4
Fan motor
Maximun external static pressure
(Pa)
50
70
70
70
70
70
70
70
70
Sound levels
Supply sound power level (speeds
2/3/5) (3)
(dB(A))
39/45/
47
38/46/
47
45/50/
54
42/48/
51
42/49/
52
46/53/
57
50/54/
58
47/50/
54
39/43/54
Return sound power level (speeds
2/3/5) (3)
(dB(A))
42/48/
50
43/49/
51
47/52/
55
45/50/
53
40/47/
51
51/56/
59
53/56/
59
50/53/
56
42/46/67
Radiated sound power level
(speeds 2/3/5) (3)
(dB(A))
31/40/
44
31/40/
43
33/42/
47
33/41/
47
42/48/
53
42/48/
53
44/48/
53
44/49/
53
37/41/52
NR Level (speeds 2/3/5) (4)
20/25/
27
18/25/
27
24/31/
34
24/31/
34
22/30/
34
27/33/
36
31/34/
37
27/30/
33
20/24/34
NC Level (speeds 2/3/5) (4)
18/23/
25
16/23/
26
23/29/
33
23/29/
32
20/28/
33
25/32/
35
29/32/
35
26/28/
32
18/22/
32
Speed 1/5/6 -> speed low/medium/high
(1) At medium speed in compliance with Eurovent conditions
(2) EER Eurovent ratio and class definition (speed (low/medium/high)
(3) Levels according to Eurovent specification 8/2 (ISO 3741/88) and Eurovent FC Certification
(4) Values calculated from sound levels with hypothetical acoustic attenuation of 20dB
(*) FCD 204/304 performance at speeds 1/4/5 : sound power at speeds 2/3/4
UNT-SVX10G-BAT1_Mise en page 1 7/26/2013 2:41 PM Page 8